Helios Large Display Pulse Input Batch Controller Instruction Manual
PD2-6310
24
Controller Operation
The PD2-6210 controller is capable of accepting pulses (e.g. ±40mV to ± 8V), square wave (0-5, 0-12V,
or 0-24V), open collector NPN, PNP, TTL, or switch contact signals. These signals are scaled to
represent rate in engineering units from -99999 to 999999. The pulse signals may be scaled with a K-
factor to represent a total for the batch, and grand total.
The default configuration displays batch total on the upper display, and a selection of rate, grand total,
batch count, and preset on the lower display.
When in pause or stop mode, the display will alternate the numeric value with the run status in the upper
display and the display label for the lower display.
The controller has up to 4 relays on board which are used to either control the batch process in single or
multi-stage batch control, or as alarms that will be active when the batch process is running. A 4-20 mA
output option is also available for retransmitting the process variable analog signal.
Default Batch Control Operation
The following describes the operation of the three operating buttons as programmed with default settings.
START Button
Press the START button to begin a new batch process.
BATCH Button
Press the Batch button to access the Preset (batch amount) menu. Program the batch with the arrow
keys, and confirm with the Enter key.
STOP Button
Press the STOP key once during a batch to pause. Press the STOP key while paused to stop and
cancel the batch. Press the STOP key while in stop/ready mode cycle lower display values of rate (or
other lower display programmed parameter), grand total, batch count, and preset.
Only STOP Button Enabled if a Batch is Running
During a batch process, only the pause/stop
functions of the STOP button will function. No other
buttons will be functional.
!
www.
GlobalTestSupply
.com
Find Quality Products Online at: