Helios Large Display Dual-Input Meter Instruction Manual
PD2-6060
48
Display
Parameter Action/Setting
F3
F3 function
key
Assign F3 function
key
F4
F4 function
Assign F4 function
(digital input)
dI I
Digital
input 1
Assign digital input 1
– 4, if expansion
modules are
connected
dO 1
Digital
output 1
Assign digital output
1 – 4, if expansion
modules are
connected
ICal
Internal
source
calibration
Enter internal source
calibration (used for
scaling the meter
without a signal
source)
Ch-A
Channel A
Perform calibration
on channel A
Ch-b
Channel B
Perform calibration
on channel B
C CAL
Current
calibration
Calibrate 4-20 mA
current input
(internal reference
source used for
scaling the input)
Display
Parameter Action/Setting
C lo
Current low
Calibrate low current
input (e.g. 4 mA)
C Hi
Current
high
Calibrate high
current input (e.g. 20
mA)
v CAL
Voltage
calibration
Calibrate voltage
input
v Lo
Voltage low
Calibrate low
voltage input (e.g. 0
V)
v Hi
Voltage
high
Calibrate high
voltage input (e.g.
10 V)
Diag
Diagnostics
Display parameter
settings
LED t
LED test
Test all LEDs
Info
Information
Display software
and S/N information
Erase
Erase
Delete the
MeterView Pro
installation files from
the meter
Noise Filter (
filter
)
The noise filter is available for unusually noisy signals that
cause an unstable process variable display. The noise
filter averages the input signal over a certain period. The
filter level determines the length of time over which the
signal is averaged. The filter level can be set between 2 and 199. The
higher the filter level, the longer the averaging time and so the longer it
takes the display to settle to its final value. Setting the filter level to zero
disables the filter function.
Noise Filter Bypass (
bypass
)
The noise filter bypass changes the behavior of the meter
so that small variations in the signal are filtered out but
large abrupt changes in the input signal are displayed
immediately. The bypass value determines the minimum
amount of signal change to be displayed immediately. All signal changes
smaller than the bypass value are filtered or averaged by the meter. The
noise filter bypass may be set between 0.1 and 99.9% of full scale.