PD301 - PD306 Smart Temp Transmitters
Instruction Manual
28
Calibration
For most applications it should not be necessary to calibrate the
4-20 mA output. Instead of Calibration use the Parameter Setup to set
the 4-20 mA output values.
If a precise calibration is needed for a specific input type and range,
follow the steps below:
1. Connect a calibrated signal source to the input.
2. Apply the low value signal at which 4 mA will be generated.
3. Click on Calibration to 4 mA.
4. Apply the high value signal at which 20 mA will be generated.
5. Click on Calibration to 20 mA.