PD301 - PD306 Smart Temp Transmitters
Instruction Manual
14
INSTALLATION
For hazardous area applications, the installer is responsible for
following all the appropriate hazardous area installation requirements.
For Installation in USA:
The Smart Temperature Transmitter must
be installed in accordance with the National Electrical Code (NEC)
NFPA 70.
For Installation in Canada:
The Smart Temperature Transmitter
must be installed in accordance with the Canadian Electrical Code
CSA 22.1.
For European Community:
The Smart Temperature Transmitter
must be installed in accordance with the ATEX directive 94/9/EC; the
enclosure certificates ATEX CERT: Sira09ATEX1023U and IECEx
CERT: SIR 09.0006U.
All wiring connectors are accessed by opening the connection head
cover. It is not necessary to remove temperature transmitter from the
connection head during installation.
Models PD303 and PD305 should be configured in a safe area prior
to installation, using the USB adapter and PC software. Models
PD304 and PD306 configuration and programming can be performed
through the HART communication interface by accessing the loop and
following all the hazardous area safety procedures.
!
CAUTION
: Disconnect from supply before opening enclosure.
Keep cover tight while circuits are alive. Conduit seals must be
installed within 18" of the enclosure.