5131V104-UK
11
Electrical specifications, mA / V / mV input:
Current input:
Measurement range ................................................ 0...100 mA
Min. measurement range (span) ........................ 4 mA
Max. offset ................................................................. 50% of selec. max. value
Input resistance:
Supplied unit.............................................................. Nom. 10
Ω
+ PTC 10
Ω
Non-supplied unit .................................................... RSHUNT =
∞
, VDROP < 6 V
Voltage input:
Measurement range ................................................ 0...250 VDC
Min. measurement range (span) ........................ 5 mVDC
Max. offset ................................................................. 50% of selec. max. value
Input resistance
≤
2,5 VDC ................................ Nom. 10 M
Ω
> 2,5 VDC ................................ Nom. 5 M
Ω
Electrical specifications - OUTPUT:
Signal range (span) ................................................. 4...20 mA
Min. signal range (span) ........................................ 10 mA
Max. offset ................................................................. 50% of selec. max. value
Load resistance.........................................................
≤
(V
supply
-7.5) / 0.023 A) [
Ω
]
Load stability .............................................................
≤
0.01% of span / 100
Ω
Current limit ...............................................................
≤
28 mA
Sensor error detection:
Programmable ........................................................... 3.5...23 mA
NAMUR NE43 Upscale ........................................... 23 mA
NAMUR NE43 Downscale ..................................... 3.5 mA
No function ................................................................ Not defined
EEx / I.S. approval (5131B):
DEMKO 99ATEX124572
.......................................
II (1) GD
[EEx ia] IIC
Applicable for ............................................................ Zone 0, 1, 2, 20, 21 or 22