HART
®
TRANSPARENT DRIVER
PRetrans 5107
• 1- or 2-channel version
• 3- / 5-port 3.75 kVAC galvanic isolation
• < 1.3 V voltage drop on input
• 16 V driving voltage on Ex output
• Universal supply by AC or DC
Application:
• Safety barrier for current signals and 2-way HART
®
communication transmit-
ted to I/P converters mounted in hazardous area.
• Safety barrier for 2-way HART
®
communication and analogue current signals
transmitted to hazardous area.
• Signal isolator with low response time on analogue current signals transmitted
to hazardous area.
Technical characteristics:
• PR’s HART
®
transparent driver primarily processes current signals of 4...20
mA.
• PR5107B is based on microprocessor technology for gain and offset. The
analogue signal is transmitted at a response time of less than 25 ms.
• Inputs, outputs, and supply are floating and galvanically separated.
Mounting / installation:
• Mounted vertically or horizontally on a DIN rail. As the modules can be moun-
ted without distance between neighbouring units, up to 84 channels can be
mounted per metre.
21
HOW TO DISMANTLE SYSTEM 5000
First, remember to demount the connectors with hazardous voltages.
Picture 1:
By lifting the bottom lock, the module
is detached from the DIN rail.
Picture 2:
Then, by lifting the upper lock and
pulling the front plate simultane-
ously, the PCB is removed.
Switches and jumpers can now be
adjusted.