5333V113-UK
5
General values
Input type
Absolute
accuracy
Temperature
coefficient
All
≤
±0.1% of span
≤
±0.01% of span / °C
Basic values
Input type
Basic
accuracy
Temperature
coefficient
RTD
≤
±0.3°C
≤
±0.01°C/°C
Lin. R
≤
±0.2
Ω
≤
±20 m
Ω
/ °C
EMC immunity influence ........................................... < ±0.5% of span
Accuracy, the greater of general and basic values:
Effect of supply voltage variation ....................
≤
0,005% of span / VDC
Vibration ...................................................................... IEC 60068-2-6 : 2007
2...25 Hz ..................................................................
±1.6 mm
25...100 Hz ...................................................... ±4 g
Max. wire size ............................................................ 1 x 1.5 mm
2
stranded wire
Humidity ...................................................................... < 95% RH (non-cond.)
Dimensions ................................................................. Ø 44 x 20.2 mm
Protection degree (enclosure / terminal) ....... IP68 / IP00
Weight .......................................................................... 50 g
Electrical specifications, input:
RTD and linear resistance input:
Max. offset ................................................................. 50% of selec. max. value
Cable resistance per wire (max.) ....................... 10
Ω
Sensor current ........................................................... > 0.2 mA, < 0.4 mA
Effect of sensor cable resistance
(3-wire) ........................................................................ < 0.002
Ω
/
Ω
Sensor error detection ........................................... Yes
RTD
type
Min.
value
Max.
value
Min.
span
Standard
Pt100
Ni100
Lin. R
-200°C
-60°C
0
Ω
+850°C
+250°C
10000
Ω
25°C
25°C
30
Ω
IEC 60751
DIN 43760
-----