4222V101-UK 17
Sensor error detection limits
Signal conditioning limits
Error indications
Outside range readout (IN.LO, IN.HI):
If the valid range of the A/D converter or the polynomial is exceeded.
Input
Range
Readout
Limit
VOLT
0...1 V / 0.2...1 V
IN.LO
< -25 mV
IN.HI
> 1.2 V
0...2.5 / 0.5...2.5 / 0...5 V / 1...5 V /
0...10 V / 2...10 V
IN.LO
< -25 mV
IN.HI
> 12 V
CURR
0...20 mA / 4...20 mA
IN.LO
< -1.05 mA
IN.HI
> 25.05 mA
LIN.R
0...800
Ω
IN.LO
< 0
Ω
IN.HI
> 1075
Ω
0...10 k
Ω
IN.LO
< 0
Ω
IN.HI
< 110 k
Ω
POTM
Min. readout = 0%, Max. readout = 100%
IN.LO
< -0.5 %
IN.HI
> 100.5 %
TEMP
TC / RTD
IN.LO
< temperature range -2°C
IN.HI
> temperature range +2°C
Sensor error detection (SE.BR, SE.SH):
Input
Range
Readout
Limit
CURR
Loop break (4...20 mA)
SE.BR
<= 3.6 mA; > = 21 mA
POTM
All, SE.BR on all 3-wire
SE.BR
> ca. 126 k
Ω
LIN.R
0...800
Ω
SE.BR
> ca. 875
Ω
0...10 k
Ω
SE.BR
> ca. 11 k
Ω
TEMP
TC
SE.BR
> ca. 750 k
Ω
/ (1,25 V)
RTD: 2-, 3- and 4-wire
No SE.SH for Pt10, Pt20 and Pt50
SE.BR
> ca. 15 k
Ω
SE.SH
< ca. 15
Ω
Readout at hardware error
Error search
Readout
Cause
Test of internal CJC sensor
CJ.ER
CJC sensor defect or
tem perature outside range
Checksum test of the configuration in FLASH
FL.ER
Error in FLASH
Communications test 4501 / 4222
NO.CO
Connection error
Check that input signal matches input configuration
IN.ER
1) Error levels on input
Check that saved configuration in 4501 matches module
TY.ER
Configuration is not 4222
! All error indications flash once per second. The help text explains the error.
1) The error is reset by switching off and then switching on the supply voltage to the module.