38
HumiTherm Ultra
User Manual
Factory
Detection Enable
Options No, Yes
:
Default :
No
Set to ‘Yes’ if Door Open detection switch is mounted.
Door Open Logic
Options : Switch Open, Switch Close
Default : Switch Close
If this parameter is set to ‘Switch Close’, the door is detected as
if the switch is CLOSE. If this parameter is set to ‘Switch
Open
Open’, the door is detected as
if the switch is OPEN.
Open
Alarm Delay (Sec.)
Range : 0 to 1000 Sec.
Default : 60 Sec.
This parameter sets a timer. From the time the door is opened, the timer begins counting down. If the door is not closed before
the timer reaches 0, the
alarm is activated.
Door Open
Door Open
Factory
Power Fail