37
HumiTherm Ultra
User Manual
Factory
Float Detection Enable
Options No, Yes
:
Default :
No
Set to ‘Yes’ if Float Switch is mounted for detecting Low water level.
Float Low Level Logic
Options : Switch Open, Switch Close
Default : Switch
Close
If set to ‘Switch Close’, the water level is considered Low if the switch is CLOSE. If set to ‘Switch Open’, the water level is
considered Low if the switch is OPEN.
Thermostat Detection Enable
Options No, Yes
:
Default :
No
Set to ‘Yes’ if Thermostat is mounted for detecting Low water level.
Thermostat Low Level Logic
Options : Switch Open, Switch Close
Default : Switch Close
If set to ‘Switch Close’, the water level is considered Low if the thermostat contacts are CLOSE. If set to ‘Switch Open’, the
water level is considered Low if the thermostat contacts are OPEN.
Common Boiler
Options : No, Yes
Default : No
This parameter is shown on the screen only if Standby Control Gadget option is enabled / installed. Set this parameter to ‘Yes’
if both, Main and Standby, heaters are mounted in a single steam generating boiler. In this case, only a single pair of Float
Switch & Thermostat is used and connected to Main Digital Inputs.
Water Level