Appendix I
128
Ap
p
en
d
ix
I
101D
Communication set value
101F
Master-frequency display
1020
Auxiliary frequency display
Note:
There are two ways to modify the settings frequencies through communication mode:
The first: Set F0.03 (Main frequency source setting) as 0/1 (keyboard set frequency), and then
modify the settings frequency by modifying F0.01 (keyboard set frequency). Communication
mapping address of F0.01 is 0xF001 (Only need to change the RAM communication mapping
address to 0x0001).
The second:Set F0.03 (Main frequency source setting) as 9 (Remote communication set), and
then modify the settings frequency by modifying (Communication settings). , mailing address of
this parameter is 0x1000.The communication set value is the percentage of the relative value,
10000 corresponds to 100.00%, -10000 corresponds to -100.00%. For frequency dimension data, it
is the percentage of the maximum frequency (F0.19); for torque dimension data, the percentage is
F5.08 (torque upper limit digital setting).
Control command is input to the inverter: (write only)
Command word address
Command function
2000
0001: Forward run
0002: Reverse run
0003: Forward Jog
0004: Reverse Jog
0005: Free stop
0006: Deceleration and stop
0007: Fault reset
Inverter read status: (Read-only)
Status word address
Status word function
3000
0001: Forward run
0002: Reverse run
0003: Stop
Parameter lock password verification: (If the return code is8888H, it indicates that password
verification is passed)
Password address
Enter password
C000
*****
Digital output terminal control: (write only)
Command address
Command content
2001
BIT0: SPA output control
BIT1: RELAY2 output control
BIT2 RELAY1 output control
BIT3: Manufacturer reserves the undefined
BIT4: Reserve