Installation
27
Powerware
®
9125 Two-in-One (5000/6000 VA) PDM User’s Guide
S
Rev B
www.powerware.com
Output Line 2, 208
–240V
Output Neutral
Output
Ground
Input L1
Input L2
Input
Ground
120V
Output -120V
Output Line 1, 208
–240V
E4 1
2
3
4
5
6 7 E5
Figure 13. PPDM HW Model Terminal Block
Table 3. PDM Wiring Specifications
Terminal
PDM Wire Function
Terminal Wire
Tightening
Terminal
Position
PPDM EURO HW
PPDM HW
Terminal Wire
Size Rating*
Tightening
Torque
1
Input Line 1
Input Line 1
2
Input Line 2/N
Input Line 2
3
Output 230–240V (Isolated)
Output -120V
2
4
Output 115–120V
120V
2–17 mm
2
(14–6 AWG)
1.8
±
0.22 Nm
(16
±
2 in lb)
5
Output Neutral
Output Neutral
(14–6 AWG)
(16
±
2 in lb)
6
Output Line 1, 230–240V
Output Line 1, 208–240V
7
Output Line 2/N, 230–240V Output Line 2, 208–240V
E4
Input Earthing
Input Ground
2–5 mm
2
(14–10 AWG)
8 mm
2
2.26
±
0.22 Nm
(20
±
2 in lb)
2.82
±
0.22 Nm
E5
Output Earthing
Output Ground
8 mm
(8 AWG)
17 mm
2
(6 AWG)
2.82
±
0.22 Nm
(25
±
2 in lb)
3.95
±
0.22 Nm
(35
±
2 in lb)
*Use 2.0 mm
2
(14 AWG) 75
_
C copper wire minimum.
11.
Replace the wiring access cover and the conduit landing plate.
12.
Plug the input and output cords of the PDM into the input and
output power connectors on the UPS rear panel.
Содержание 9125 PowerPass
Страница 2: ......
Страница 6: ...Table of Contents ii Powerware 9125 Two in One 5000 6000 VA PDM User s Guide S Rev B www powerware com...
Страница 16: ...Introduction 10 Powerware 9125 Two in One 5000 6000 VA PDM User s Guide S Rev B www powerware com...
Страница 40: ...Configuration 34 Powerware 9125 Two in One 5000 6000 VA PDM User s Guide S Rev B www powerware com...
Страница 44: ...Specifications 38 Powerware 9125 Two in One 5000 6000 VA PDM User s Guide S Rev B www powerware com...
Страница 54: ...Service and Support 48 Powerware 9125 Two in One 5000 6000 VA PDM User s Guide S Rev B www powerware com...
Страница 55: ......
Страница 56: ...B B...