9125 Two-in-One (5000/6000 VA) PDM User’s Guide
S
Rev B
www.powerware.com
Table 2. Hardwired PDM Input/Output Voltage Settings
PPDM HW, and PPDM EURO HW Models
Input Voltage
PDM Output Voltage
Input Voltage
(from UPS)
208V Switch Position
(HV/LV)
Default 240V Switch Position
(HV/LV)
208
208/120
208/104
220
220/126
220/110
230
230/131
230/115
240
240/136
240/120
6.
Remove the wiring access cover and the conduit landing plate
and retain (see Figure 11).
Punch holes in the conduit landing plate for the input and
output conduit using a Greenlee
®
punch or similar device.
7.
Pull the input and output wires through separate conduit,
leaving approximately 2 ft (0.5m) of exposed wire. Attach a
flexible metal fitting to the end of each conduit.
8.
Insert each conduit through a wiring access entry and attach the
conduit fitting to the panel. Strip 0.35
I
(9 mm) of insulation
from the end of each incoming wire.
Содержание 9125 PowerPass
Страница 2: ......
Страница 6: ...Table of Contents ii Powerware 9125 Two in One 5000 6000 VA PDM User s Guide S Rev B www powerware com...
Страница 16: ...Introduction 10 Powerware 9125 Two in One 5000 6000 VA PDM User s Guide S Rev B www powerware com...
Страница 40: ...Configuration 34 Powerware 9125 Two in One 5000 6000 VA PDM User s Guide S Rev B www powerware com...
Страница 44: ...Specifications 38 Powerware 9125 Two in One 5000 6000 VA PDM User s Guide S Rev B www powerware com...
Страница 54: ...Service and Support 48 Powerware 9125 Two in One 5000 6000 VA PDM User s Guide S Rev B www powerware com...
Страница 55: ......
Страница 56: ...B B...