A---10
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual
164201408
Rev. P00 053002
DESCRIPTION:
DRAWING NO:
1 of 1
SHEET:
Remote Interface Connections
164201408--3
1
CB1
AUXI
L
IAR
Y
SWI
T
C
H
(N/C)
CB1
AUXI
L
IAR
Y
SWI
T
C
H
(COM
M
)
CB1
AUXI
L
IAR
Y
SWI
T
C
H
(N/O)
CB1
ST
(--
)
C1
1
CB1
ST
(+
)
C
12
CB1
AUXI
L
IAR
Y
SWI
T
C
H
(N/C)
CB1
AUXI
L
IAR
Y
SWI
T
C
H
(COM
M
)
CB1
AUXI
L
IAR
Y
SWI
T
C
H
(N/O)
CB1
ST
(--
)
CB1
ST
(+
)
TB1
Notes:
1. Shunt trip requires 24V (150 VA instantaneous) to activate (supplied by user).
2. Auxiliary switches are rated as follows:
240 VAC @ 15A
125 VDC @ 0.3A
250 VDC @ 0.15A
3. Wiring shall be suitable for Class 1, 600V wiring methods.
Note 2,3,4
Note 2,3,4
Note 1
Note 1
4. Torque screw terminals to 20 in.-lb.
All wiring shall be #10-22 AWG, 75 deg. C minimum.
2 3 4 5 6 7 8 9
11
10
12