35
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual
164201408 Rev. P00 053002
T
A
E
T
T
T
T
T
T
T
E
E
E
E
E
A
A
A
A
A
Figure 21. Knockout Pattern for Remote Battery Disconnect
Table A. Remote Battery Disconnect Power Terminations
Terminal
Size of Pressure Termination
Terminal Function
E4 (+)
1 --- #8---3/0
UPS Battery Contactor K2 (+)
E5 (---)
1 --- #8---3/0
UPS Battery Contactor K2 (---)
Breaker (+)
1 --- #4---300 kcmil
Battery Disconnect (+)
Breaker (---)
1 --- #4---300 kcmil
Battery Disconnect (---)
Breaker (jumper)
1 --- #4---300 kcmil
Battery Disconnect (jumper)
Battery Cabinet (+)
See Table C (Appendix A)
Stand---alone battery cabinet (+)
Battery Cabinet (---)
See Table C (Appendix A)
Stand---alone battery cabinet (---)
Table B. Battery Cabinet Terminations
Battery Cabinet
Size of Pressure Termination
Series 685
(1) #2---1/0 kcmil [Breaker (+) & (---)]
Series 1085
(1) 3/0---250 kcmil [Breaker (+) & (---)]