ENGLISH
make sure the load equipment is turned off before plugging all loads into the output
receptacle.
IV.
Connecting the Multiple EBMs
1000VA/1500VA/2000VA and 3000VA UPS include external battery port that allows users
to connect multiple EBM in order to provide additional backup time. Follow the
procedure to install multiple EBM as below.
V.
Connecting multiple EBMs in Tower form
1.
Connect Earth line between UPS and the
first EBM, and then connect Earth Line
between the first EBM and the second
EBM.
2.
Take off the front panel, and connect the
battery terminal (A) from UPS to EBM
terminal (B) shown as below. And then
connect the battery terminal (D) from the
first EBM to the battery terminal (E) from
the second EBM. Users need to remove
the small gate(C) on side of the front
panel to allow the outlet wire of the EBM
to pass through the gate and then
reassemble front panel.
VI.
Connecting the Multiple EBMs in rack form
1.
Connect Earth line between UPS and the first EBM, and then connect Earth Line between
the first EBM and the second EBM.
B
C
A
D
E