3-4
CAUTION
If battery systems are located in the same room as the UPS, the battery manufacturer's
environmental requirements should be followed if they are more stringent than the UPS
requirements. Operating temperatures above the recommended range will result in decreased
battery life and performance, and may reduce or void the battery warranty.
The UPS ventilation requirements are shown in Table 3-4.
Table 3-4. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Model
Heat Rejection
BTU/hr x1000 (kg-cal/hr)
Input / Output Voltage
VFI 20000TAP 3/3 BI
2
0000
VA
380/380 400/400 415/415
1149
VFI 20000TAP 3/3 BE
20
000 VA
380/380 400/400 415/415
1149
VFI 30000TAP 3/3 BI
30
000 VA
380/380 400/400 415/415
1723
VFI 30000TAP 3/3 BE
30
000 VA
380/380 400/400 415/415
1723
VFI 40000TAP 3/3 BI
40
000 VA
380/380 400/400 415/415
2298
VFI 40000TAP 3/3 BE
40
000 VA
380/380 400/400 415/415
2298
VFI 60000TAP 3/3 BX
60
000 VA
380/380 400/400 415/415
3447
VFI 80000TAP 3/3 BX
80
000 VA
380/380 400/400 415/415
4596
Содержание VFI 20000-40000TAP 3/3 BI
Страница 2: ......
Страница 4: ......
Страница 8: ...iv This page intentionally left blank...
Страница 10: ...vi This page intentionally left blank...
Страница 12: ...viii This page intentionally left blank...
Страница 18: ...1 6 This page intentionally left blank...
Страница 21: ...Section 1 Installation...
Страница 22: ......
Страница 46: ...This page intentionally left blank 3 24...
Страница 64: ...4 18 Notes...
Страница 65: ...Section 2 Operation...
Страница 66: ......
Страница 100: ...This page intentionally left blank 7 2...