ARTICULATED ARM OPENERS USER MANUAL
13
1. F9-1
Type of Safety Device
FULLY CLOSED
FULLY OPENED
STOP DURING MOVING
CLOSING
OPENING
Safety Device2 :
Photocell-OPEN
Open not allowed
No effect
Open not allowed
No effect
Close
Safety Device1 :
Photocell-CLOSE
No effect
Reload automatic closing time
Reload automatic closing time
Open
No effect
Position of Gate
When safety devices are activated
2. F9-2
Type of Safety Device
FULLY CLOSED
FULLY OPENED
STOP DURING MOVING
CLOSING
OPENING
Safety Device2 :
Safety Edge
Open not allowed
Locks
Reverse to open for 2 seconds
Reverse to clsoe for 2 seconds
Reload automatic closing time
Safety Device1 :
Photocell-CLOSE
No effect
Reload automatic closing time
Open
No effect
Position of Gate
When safety devices are activated
3. F9-3
Type of Safety Device
FULLY CLOSED
FULLY OPENED
STOP DURING MOVING
CLOSING
OPENING
Safety Device2 :
Opening Device
Open
Open
Open
No effect
Reload automatic closing time
Safety Device1 :
Photocell-CLOSE
No effect
Reload automatic closing time
Open
No effect
Position of Gate
When safety devices are activated
4. F9-4
Type of Safety Device
FULLY CLOSED
FULLY OPENED
STOP DURING MOVING
CLOSING
OPENING
Safety Device2 :
Photocell-OPEN/CLOSE
Open not allowed
Locks
Stop
Stop
Close not allowed, Open for 2 seconds when auto closing is ON
Safety Device1 :
Photocell-CLOSE
No effect
Close not allowed
Open
No effect
Position of Gate
When safety devices are activated
3.2 Photocell Adjustment
The actions of the photocells safety edge loop detector when they detecting obstacles.