CHAPTER 5—COMMUNICATIONS
Onboard Communications Capabilities
Table 5 – 1: 2-wire, RS485 Port Capabilities
Communications Port
RS485:
•
2-wire with shield
•
EIA compliant
•
Allows the power meter to be
connected to a daisy-chain of up to 32
devices
Baud Rate
9600
19200
38400
Communications Distances
See Table 5 – 2.
Protocols
Modbus RTU
Jbus
7-, 8-bit ASCII
Parity
ODD
EVEN
NONE
Table 5 – 2: 2-wire, RS485 Communications Distances
Baud Rate
Maximum Communication Distances
1 to 32 Devices
Feet
Meters
9600
8,000
2,438
19200
6,000
1,829
38400
3,000
914
NOTES:
•
Distances are for 2-wire devices and 4-wire devices configured for 2-wire operation,
such as the Series 600 Power Meter and the Series 3000 and 4000 Circuit Monitor.
•
Distances listed should be used as a guide only and cannot be guaranteed for non-
POWERLOGIC devices. Refer to the master device’s documentation for any
additional distance limitations.