© 2006 Schneider Electric All Rights Reserved
PowerLogic
®
Series 800 Power Meter
63230-500-224A1
Chapter 3—Installation
6/2006
EN–14
EN
GLI
S
H
•
For European Community (
CE)
compliance, the disconnect circuit
breaker must be placed within reach of the power meter and
labeled:
Disconnect Circuit Breaker for Power Meter
.
NOTE: The disconnect circuit breaker must be rated for the short
circuit current at the connection points.
•
Locate the power meter in an area where ambient conditions fall
within the acceptable range. For control power voltages above
300 Vac, the temperature range for the meter block is -25°C to
+65°C. The front display has a range of -10°C to +50°C.
NOTE: Ambient temperature refers to the immediate environment
of the power meter, including the temperature within the
enclosure in which it is mounted.
CAUTION
IMPROPER VENTILATION
• Only mount the power meter as described in this instruction
bulletin.
• Provide the clearances around the power meter as illustrated in
Figure 3 – 1, Figure 3 – 2, and Figure 3 – 3.
Failure to follow this instruction can result in equipment damage.
Содержание PM820
Страница 2: ......