© 2006 Schneider Electric  All Rights Reserved

63230-500-224A1

PowerLogic

®

 Series 800 Power Meter

6/2006

Chapter 4—Wiring

EN–29

ENGLISH

Figure 4 – 1: 

1-Phase Line-to-Neutral 2-Wire 
System 1 CT

Figure 4 – 2: 

2-Phase Line-to-Line 2-Wire System 
1 CT

NOTES:

To avoid distortion, use parallel wires for control 
power and voltage inputs. Keep the fuse close to 
the power source.

Use system type 10.

NOTES: 

To avoid distortion, use parallel wires for control 
power and voltage inputs. Keep the fuses close to 
the power source.

Use system type 11.

Figure 4 – 3: 

2-Phase 3-Wire Direct Voltage 
Connection 2 CT

Figure 4 – 4: 

3-Phase 3-Wire 2 CT no PT

NOTE:

To avoid distortion, use parallel wires for control 
power and voltage inputs. Keep the fuses close to 
the power source.

Use system type 12.

NOTES:

Use system type 30.

N L1

PM

8

00

8

9

10
11

12

1

3

14

15
16

17

S

2

S

1

PL

SD11

0051

PM800

L1 L2

8

9

10
11

12

13
14

15
16

17

VL-L=< 600V

S2

S1

PL

SD11

0050

L1 L2

N

PM800

8

9

10
11

12

13
14

15
16

17

S2

S1

S2

S1

PLS

D

110

049

L1 L2 L3

PM800

8

9

10
11

12

13
14

15
16

17

S2

S1

S2

S1

PL

SD11

0054

Содержание PM820

Страница 1: ...e la serie 800 Centrale de mesure de la s rie 800 PM820 PM850 PM870 63230 500 224A1 6 2006 Retain for future use Cons rvese para futuras consultas conserver pour une utilisation ult rieure Installatio...

Страница 2: ......

Страница 3: ...injury hazards Obey all safety messages that follow this symbol to avoid possible injury or death NOTE Provides additional information to clarify or simplify a procedure PLEASE NOTE Electrical equipme...

Страница 4: ...nce when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction man...

Страница 5: ...Meter Without Display 20 DIN Rail Mounting 20 Power Meter With Remote Display 21 PM8RDA Dimensions 21 PM8RDA Installation 22 PM8RD Dimensions and Mounting Options 23 Square Cutout 23 Surface Mount for...

Страница 6: ...Up CTs 51 Set Up PTs 52 Set Up Frequency 52 Set Up the Meter System Type 53 Power Meter With Integrated Display Communications Setup 53 Power Meter With Remote Display Communications Setup 54 Comm1 S...

Страница 7: ...to install and set up a PowerLogic Series 800 Power Meter Unless otherwise noted the information contained in this manual refers to the following Power Meters Power Meter with integrated display Power...

Страница 8: ...he SMS setup guide which is available in English French and Spanish See Table 1 1 for a list of power meter models supported by SMS NOTE For additional information download the reference manual at pow...

Страница 9: ...control power to the power meter 2 Voltage inputs Voltage metering connections 3 I O connector KY pulse output digital input connections 4 Heartbeat LED A green flashing LED indicates the power meter...

Страница 10: ...art Description 1 Control power supply connector Connection for control power to the power meter 2 Voltage inputs Voltage metering connections 3 I O connector KY pulse output digital input connections...

Страница 11: ...ction between the remote display and the power meter and provides an additional RS232 RS485 connection 2 or 4 wire 2 Cable CAB12 Connects the remote display to the remote display adapter 3 Remote disp...

Страница 12: ...PM820RD PM850RD PM870RD PM820RDMG PM850RDMG PM870RDMG Accessories Remote Display with Remote Display Adapter PM8RD PM8RDMG Remote Display Adapter PM8RDA Input Output Modules PM8M22 PM8M26 PM8M2222 Ca...

Страница 13: ...Lugs Plug set Terminator MCT2W Power Meter installation manual Power Meter without Display Power Meter without display Hardware kit 63230 500 16 containing Two retainer clips Template Install sheet L...

Страница 14: ...adings THD 9 9 9 Downloadable firmware 9 9 9 Easy setup through the integrated or remote display password protected 9 9 9 Setpoint controlled alarm and relay functions 9 9 9 Onboard alarm logging 9 9...

Страница 15: ...irmware Version on page EN 56 for instructions on how to determine the firmware version To download the latest firmware version follow the steps below 1 Using a web browser go to http www powerlogic c...

Страница 16: ...2006 Schneider Electric All Rights Reserved PowerLogic Series 800 Power Meter 63230 500 224A1 Chapter 1 Introduction 6 2006 EN 10 ENGLISH...

Страница 17: ...er supplying this equipment before working on or inside equipment Always use a properly rated voltage sensing device to confirm that all power is off Beware of potential hazards and carefully inspect...

Страница 18: ...2006 Schneider Electric All Rights Reserved PowerLogic Series 800 Power Meter 63230 500 224A1 Chapter 2 Safety Precautions 6 2006 EN 12 ENGLISH...

Страница 19: ...y for Power Meter Models and Accessories Description Model Number Section Square D Merlin Gerin Power Meters Power Meter with Integrated Display PM820 PM850 PM870 PM820MG PM850MG PM870MG Dimensions on...

Страница 20: ...ter in an area where ambient conditions fall within the acceptable range For control power voltages above 300 Vac the temperature range for the meter block is 25 C to 65 C The front display has a rang...

Страница 21: ...62 mm in PLSD110043 DANGER HAZARD OF ELECTRIC SHOCK BURN OR ARC FLASH Apply personal protective equipment PPE and follow safe electrical work practices See NFPA 70E Only qualified workers should inst...

Страница 22: ...EN 16 ENGLISH Figure 3 2 Clearances for mounting a single power meter 20 0 787 20 0 787 5 0 197 5 0 197 106 4 174 136 5 354 PLSD110047 Figure 3 3 Clearances for mounting multiple power meters mm in 10...

Страница 23: ...cluded with the power meter make a square cut out 3 622 in x 3 622 in 92 mm x 92 mm 3 Insert the power meter through the cut out 4 Attach the two retainer clips to the power meter as shown There are t...

Страница 24: ...iver into the engraved slot of one of the clips on the display b Gently but firmly pull the screwdriver towards the front of the power meter display until the clip releases Be sure to hold the display...

Страница 25: ...All Rights Reserved 63230 500 224A1 PowerLogic Series 800 Power Meter 6 2006 Chapter 3 Installation EN 19 ENGLISH Figure 3 4 Installing a power meter into an existing 4 5 in round cut out PM8G PLSD11...

Страница 26: ...Without Display DIN Rail Mounting 1 Refer to Installation Considerations on page EN 13 2 Place the power meter so that the slot in the base rests on one edge of the DIN rail and snap it into place sec...

Страница 27: ...lay adapter A Power Meter without a display PM8XXU models can be used with a remote display kit PM8RD PM8RDA Dimensions NOTE Refer to Installation Considerations on page EN 13 Dimensions on page EN 15...

Страница 28: ...NT You must ground yourself and discharge any static charge before removing or attaching the display Failure to follow this instruction can result in equipment damage A PM8RDA B Snap hooks C Connector...

Страница 29: ...rsonal protective equipment PPE and follow safe electrical work practices For example in the USA see NFPA 70E Only qualified workers should install and wire the power meter Perform this work only afte...

Страница 30: ...stallation 6 2006 EN 24 ENGLISH Surface Mount for CM3000 CM4000 Display Retrofit Replacing Analog Meters 76 3 000 54 2 125 27 1 063 13 0 500 4 x 4 0 157 22 32 max 0 880 96 3 780 10 0 394 82 3 230 31 1...

Страница 31: ...e wiring connections for the power meter The following symbols are used in the diagrams NOTE The disconnect circuit breaker must be placed within reach of the power meter and labeled Disconnect Circui...

Страница 32: ...V1 V2 V3 Delta 31 No PT 4 5 4 3 I1 I2 I3 3 V1 V2 V3 Vn 4 wire Delta 40 No PT 4 6 3 I1 I2 I3 3 V1 V2 V3 Vn Wye 40 No PT 4 6 See Table 4 4 on page EN 27 for system type wiring diagrams Table 4 3 Voltage...

Страница 33: ...1 PowerLogic Series 800 Power Meter 6 2006 Chapter 4 Wiring EN 27 ENGLISH Table 4 4 System Type Wiring Diagrams Diagram System Type Delta 4 wire Delta Wye Grounded Wye NOTE In 2 PT systems these conne...

Страница 34: ...led and serviced by qualified electrical personnel Perform this work only after completely reading the installation and wiring chapters Turn off all power supplying the power meter and the equipment i...

Страница 35: ...wires for control power and voltage inputs Keep the fuses close to the power source Use system type 11 Figure 4 3 2 Phase 3 Wire Direct Voltage Connection 2 CT Figure 4 4 3 Phase 3 Wire 2 CT no PT NO...

Страница 36: ...T NOTES For an open delta PT connection with 120 V L L secondaries use system type 30 Pay close attention to polarity marks when connecting CTs S1 S2 and PTs X1 NOTES Use System type 31 For an open de...

Страница 37: ...1 NOTES Use system type 42 Pay close attention to polarity marks when connecting CTs S1 S2 and PTs X1 Figure 4 11 3 Phase 4 Wire Wye 3 wire 3 PT 2 CT for balanced 3 wire loads NOTES Use system type 40...

Страница 38: ...3 N 8 9 10 11 1 2 3 PM800 Phase to Neutral only when voltage 415 10 VAC max PLSD110071 8 9 10 11 1 2 3 DC Control Power 100 Vdc V 300 Vdc PLSD110065 L1 L2 L3 N CPT 8 9 10 11 1 2 3 PM800 Control Power...

Страница 39: ...24 125 Vdc Vac Status Switch or Auxiliary Contact Digital Output Pulse Output KY is a solid state pulse output rated for 250 VDC max or 220 Vac max Maximum load current is 100 mA at 25 C Derate 0 56...

Страница 40: ...2006 Schneider Electric All Rights Reserved PowerLogic Series 800 Power Meter 63230 500 224A1 Chapter 4 Wiring 6 2006 EN 34 ENGLISH...

Страница 41: ...ations Distances See Table 5 2 Protocols Modbus RTU Jbus 7 8 bit ASCII Parity ODD EVEN NONE Table 5 2 2 wire RS485 Communications Distances Baud Rate Maximum Communication Distances 1 to 32 Devices Fe...

Страница 42: ...d pair Belden 9841 or equivalent and the three terminal connector of the RS485 port on the power meter To connect to the power meter follow these steps 1 Strip 0 25 in 6 mm of insulation from both end...

Страница 43: ...S422 RS485 converter See Connecting the First Device on page EN 38 in this chapter for instructions If the power meter is the last device on the daisy chain terminate it See Terminating the Communicat...

Страница 44: ...link has only one device terminate that device Some POWERLOGIC devices use a removable communications connector If the last device on the communications link is not a power meter refer to the instruct...

Страница 45: ...o 2 wire converter Figure 5 5 Using a 4 to 2 wire converter to connect a PM800 to a CM2000 Notes CM2000 to CNV100 CM2000 RX Green RX White TX Red TX Black Shield Gray CNV100 RX Green RX White TX Red T...

Страница 46: ...o DEMAND POWER W o DEMAND POWER VA o WATTHOUR METER o VARHOUR METER o THD CURRENT o THD VOLTAGE o K FACTOR CIRCUIT MONITOR CT Primary PT Primary Sys Type Dmd Int WH Pulse Address Baud Rate Nom Freq R...

Страница 47: ...e instruction bulletin that ships with your Ethernet Gateway for more information and installation procedures Figure 5 7 Power meters connected to Ethernet using a POWERLOGIC Ethernet Gateway system L...

Страница 48: ...wire with shield EIA compliant Allows the power meter to be connected to a daisy chain of up to 32 devices 4 wire with shield EIA compliant Allows the power meter to be connected to a daisy chain of...

Страница 49: ...ations DANGER HAZARD OF ELECTRIC SHOCK BURN OR ARC FLASH Apply appropriate personal protective equipment PPE and follow safe electrical work practices For example in the United States see NFPA 70E Thi...

Страница 50: ...Orange stripe Connect shield to earth ground at the master port only If the display is the last device terminate it with 3090MCTAS485 terminator not included TX RX TX TX RX RX TX RX TX RX TX RX TX RX...

Страница 51: ...2 Apply control power to the meter only 3 To change to RS232 mode press and hold the mode button until the LED is lit LED is lit in RS232 mode NOTE Communications mode default is RS485 LED is unlit TX...

Страница 52: ...2006 Schneider Electric All Rights Reserved PowerLogic Series 800 Power Meter 63230 500 224A1 Chapter 5 Communications 6 2006 EN 46 ENGLISH...

Страница 53: ...e power meter How the Buttons Work The buttons are used to select menu items display more menu items in a menu list and return to previous menus A menu item appears over one of the four buttons Pressi...

Страница 54: ...en a value is selected it flashes to indicate that it can be modified A value is changed by doing the following Press or to change numbers or scroll through available options If you are entering more...

Страница 55: ...MD UNBAL V L L V L N WH VAH VARH INC PWR PHASE DMD TRUE DISPL V L L U V L N V I MINMX AMPS I VOLTS U V UNBAL PWR PQS PF HZ F THD V THD I V L L U V L N V I ACTIV HIST D OUT D IN A OUT A IN DATE TIME LA...

Страница 56: ...2006 Schneider Electric All Rights Reserved PowerLogic Series 800 Power Meter 63230 500 224A1 Chapter 6 Operation 6 2006 EN 50 ENGLISH...

Страница 57: ...e default settings are 1 Protocol Modbus RTU 2 Address 1 3 Baud rate 9600 and 4 Parity Even To begin power meter setup do the following 1 Scroll through the Level 1 menu list until you see MAINT 2 Pre...

Страница 58: ...O PT for direct connect 5 Press OK 6 Enter the PRIM primary value 7 Press OK 8 Enter the SEC secondary value 9 Press OK 10 Press1 until you are asked to save your changes 11 Press YES to save the chan...

Страница 59: ...either direct connect or with PT and D the SMS system type 6 Press OK 7 Press1 until you are asked to save your changes 8 Press YES to save the changes 0 3 3934 4 04 393 7 2 A B C D 1 Press until COM...

Страница 60: ...ess OK 7 Select the BAUD baud rate 8 Press OK 9 Select the parity EVEN ODD or NONE 10 Press OK 11 Press1 until you are asked to save your changes 12 Press YES to save the changes 3 450 2 A T N D 245 P...

Страница 61: ...GER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Do not attempt to service the power meter CT and PT inputs may contain hazardous currents and voltages Only authorized service personnel from the ma...

Страница 62: ...emory chip which has a life expectancy of up to 20 years under the operating temperature range specified for the power meter The life of the power meter s internal battery backed clock is over 10 year...

Страница 63: ...ench and Spanish Other languages are available Please contact your local sales representative for more information about other language options The power meter language can be selected by doing the fo...

Страница 64: ...tective equipment PPE and follow safe electrical work practices See NFPA 70E This equipment must be installed and serviced only by qualified personnel Turn off all power supplying this equipment befor...

Страница 65: ...esentative Control power and display if the heartbeat LED flashes but the display is blank the display is not functioning properly If the display is blank and the LED is not lit verify that control po...

Страница 66: ...ge EN 28 Initiate a wiring check using SMS Cannot communicate with power meter from a remote personal computer Power meter address is incorrect Check to see that the power meter is correctly addressed...

Страница 67: ...Category III Accuracy Current 0 075 Reading 0 025 full scale Voltage 0 075 Reading 0 025 full scale Power 0 15 Reading 0 025 full scale True Power Factor 0 002 to 0 500 leading and 0 002 to 0 500 lag...

Страница 68: ...ndard KY output Load Voltage 3 250 10 Vdc 6 220 10 Vac Isolation 1350 Vrms isolation Load Current 100 mA max at 25 C Maximum Output Frequency 25 Hz ON Resistance 50 Ohms maximum Leakage Current 0 03 A...

Страница 69: ...ing Maximum Elevation 3 000 m Pollution Degree 2 IP Rating Meter 30 Display NOTE The display must be mounted on a flat surface 52 Regulatory Standards Compliance Emissions Radiated FCC part 15 Class A...

Страница 70: ...Voltage Dips IEC 61000 4 11 Level Standards listed USA UL 61010 IEC 61010 Europe CE per EN 61010 Table A 1 Specifications Specifications based on 50 60 Hz nominal systems Full scale 10A Add 0 006 C 25...

Страница 71: ...er meter EN 15 EN 16 remote display EN 21 display button operation EN 47 changing values EN 48 menu EN 48 operation EN 47 E Ethernet Gateway connections EN 41 F features EN 8 firmware EN 9 identifying...

Страница 72: ...port EN 42 protocol EN 42 connections EN 43 mounting EN 23 EN 24 RS485 2 wire connections EN 44 RS485 4 wire connections EN 44 EN 45 route statement EN 60 RS485 onboard 2 wire EN 35 remote display 2 w...

Отзывы: