10.2 System Testing

 

 

PowerFlow E.R.S MINI is an intelligent device with no initial setup required. It automatically detects the 

import/export voltage and current, and the size of the connected loads making commissioning simple.

 

 

To check correct operation, should there be no export energy at the time of commissioning, remove the  

installed CT and re

-

install it back to front.  This will cause ERS to operate backwards, i.e import will be 

measured as export and vice versa. 

 

 

Turn a large load on such as a kettle to simulate export, ERS will detect this, as export, and start to drive 

the load connected from the main POWER OUT connection. Ensure this is on and/or calling for heat. The 

LED bar should start to illuminate progressively demonstrating operation. Allow the kettle to boil and 

switch off, you should observe the display LEDs on ERS MINI switch off. 

 

This is an indication that the device is working correctly.  

 

 

REMEMBER: Do not forget to change the CT back to the correct orientation following the test 

 

 

 

1.

 

E.R.S MINI has been mounted to a secure surface, the correct way up and with adequate 

 

 

ventilation. 

 

 

2.

 

All cable runs are correctly fixed and supported and an AC isolator has been installed. 

 

 

3.

 

The main power cable has been terminated observing the correct pin numbers. 

 

 

4.

 

Ensure all the terminations inside the consumer unit are correct and the terminals have been 

tightened.

 

 

5.

 

Ensure earth continuity between the earthing bar inside the consumer unit and one of the 

cover fixing screws on the device.

 

 

6. 

 

Carry out all circuit tests in accordance with BS7671.

 

 

7.

 

Ensure the current clamp connector has been terminated observing the correct pin numbers 

and is securely clamped around the incoming live supply conductor in the correct location. 

 

 

8.

 

Check the orientation of the current clamp to ensure the label faces the incoming supply and 

that it is installed between the main meter position and the main consumer board. 

 

 

9.

 

Ensure any safety labelling has been securely fitted in the correct locations. 

 

 

10.

 

Ensure the customer has been issued with a user manual and has been given an overview of 

 

how their system works and how to use it. 

 

 

Only energise the system once all of the above has  been completed.

 

 

 

 

 

10. Commissioning  

 

 

10.1 Energising for the first time

 

 

Before switching on for the first time, check that the following has been completed. 

 

16

 

Содержание ERS MINI

Страница 1: ...Important Information for your PowerFlow ERS MINI Installation and User Manual IMPORTANT SAFETY INFORMATION PLEASE READ AND UNDERSTAND THIS MANUAL BEFORE COMMENCING WORK...

Страница 2: ...to support Great British manufacturing By purchasing PowerFlow Products you are supporting the development of this important technology so future generations can benefit and prosper from cleaner green...

Страница 3: ...Connection panel 5 4 Ventilation mounting clearances 5 5 mounting clearances multiple devices Page 10 6 System Design 6 1 AC circuit protection Page 11 7 Connector Assemblies 7 1 Power Connections 7...

Страница 4: ...to be connected to an AC supply network with a nominal supply of 230V 50Hz ERS MINI is designed to work alongside a grid connected renewable generator such as a wind or solar system E R S MINI does no...

Страница 5: ...RS enclosure may become hot to touch Always use caution when touching the enclosure after long periods of operation 2 DO NOT place objects over the enclosure PowerFlow ERS uses the metal enclosure to...

Страница 6: ...R S MINI to work during any time of the day and together with the solar or wind generator to ensure that maximum energy capture is possible During times when export occurs the amount of energy availa...

Страница 7: ...tions should be considered prior to installation A B C D E F G H Object Quantity Description A 1 E R S MINI Device with integral mounting brackets B 1 Current measurement clamp CT C 1 1 x 3 PIN IEC Ma...

Страница 8: ...nt such as scaffolding or lifting platforms Non compliance with this recommendation may restrict servicing Extended Mounting Criteria The connection panels must always face horizontally DO NOT MOUNT U...

Страница 9: ...40mm 50mm Use 3 core 1 5mm flex to isolator then 2 5mm to consumer board IEC Power OUT connector 20mm Display Power Bar 5 2 Product Dimensions 5 3 Overview of Connection Panel Object Description A Ma...

Страница 10: ...s sufficient and suitable space for heat dissipation 5 4 Ventilation Mounting Clearances 100mm 100mm 150mm 50mm 5 5 Mounting Clearances for Multiple Devices Horizontal Installation 100mm minimum betwe...

Страница 11: ...d For further information please refer to the warranty documentation It is important to take note of the following notices Failure to do so may result in danger to persons damage to property or invali...

Страница 12: ...cable 1 5mm 3 core flex PIN 1 ERS Live OUT brown 3 PIN IEC Power IN Connector D PFM PC 03 FM Recommended cable 1 5mm 3 core flex PIN 2 Earth Green Yellow PIN 3 Neutral OUT Blue PIN 1 ERS Live IN Brown...

Страница 13: ...tive heating element connected to the ERS driven circuit Failure to observe this will result in damage IMPORTANT IMPORTANT It is essential that the current clamp CT is connected between the main prima...

Страница 14: ...not drive the load Boost button LED On start up the LED on the boost button will flash five times During manual boost operation the LED will be permanently illuminated This will switch off automatica...

Страница 15: ...o the heating load should it be required To enable the manual boost push the button once an audible click can be heard and the LED will turn on indicating the manual boost has been started At this poi...

Страница 16: ...d off The illustration below demonstrates how the display would appear in the above example 9 6 Over Temperature ERS MINI has an internal temperature sensor for safety If an over temperature situation...

Страница 17: ...up and with adequate ventilation 2 All cable runs are correctly fixed and supported and an AC isolator has been installed 3 The main power cable has been terminated observing the correct pin numbers 4...

Страница 18: ...mmersion switch next to the hot water tank must be left in the ON position Power will only be sent to the immersion heater when export energy is available Ensure there is enough export energy ERS will...

Страница 19: ...Wind Hydro Recommended renewable generator size 2 0kW Output load Resistive Only Output control range 5 100 Minimum output load 300 W Minimum export power level Export tracking range 25W 25 200W Gener...

Страница 20: ...www powerflowenergy com...

Отзывы: