14
4.4
LK10-05 freely ventilated lead-acid, with constant voltage
maintenance charging
Algorithm number: 16
Charging phase "top fill" c15 % compared to charged Ah of main phase.
Battery temperature compensation:
- voltage -3 mV / °C per cell, neutral at 30 °C
- current derated to zero in the range [-30 ... -35] and [+45 ... +60] °C