Algorithms
Verify compatibility of the algorithm with the battery manufacturer.
Notes
- "sealed" is a generic term for GEL and AGM types of lead-acid batteries, which are not freely
ventilating to surrounding air.
- Current is indicated in terms of C, which is current compared to nominal capacity. For example 0.2
C for 100 Ah battery is 20 A.
4.1
LK10-06 freely ventilated lead-acid
Algorithm number: 1
Charging phase "top fill" c15 % compared to charged Ah of main phase.
Battery temperature compensation:
- voltage -3 mV / °C per cell, neutral at 30 °C
- current derated to zero in the range [-30 ... -35] and [+45 ... +60] °C
* In maintenance phase, battery voltage is periodically checked. If it is below 2.17 V/cell, 2 minute
0.05 C current pulse is used.