8
02: Converter mode enable/disable
Interface
Setting
ENA: converter mode enable
DIS: converter mode disable (Default)
03: Output frequency setting
Interface
Setting
Output frequency can be chosen as the following:
50: output frequency 50Hz
60: output frequency 60Hz
04: Acceptable low voltage setting in Bypass mode
Interface
Setting
Press Down key or Up key to set
the acceptable bypass low voltage point(LLS):
For 200/208/220/230/240 VAC models:
170-220: low voltage setting point from 170Vac to 220Vac
(Default: 170Vac)
For 100/110/115/120/127 VAC models:
85-115: low voltage setting point from 85Vac to 115Vac
(Default: 85Vac)
05: Acceptable high voltage setting in Bypass mode
Interface
Setting
Press Down key or Up key to set
the acceptable high voltage point (HLS) in bypass mode:
For 200/208/220/230/240 VAC models:
230-264: high voltage setting point from 230Vac to 264Vac
(Default: 264Vac)
For 100/110/115/120/127 VAC models:
120-140: high voltage setting point from 120Vac to 140Vac
(Default: 132Vac)
06: Acceptable low frequency setting in Bypass/ECO mode
Interface
Setting
Press the Down key or Up key to set
the acceptable low frequency point (LLS) in bypass/ECO mode:
For 50Hz output frequency models:
45-49Hz: low frequency setting point from 45Hz to 49HZ
(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz: low frequency setting point from 55Hz to 59Hz
(Default: 57.0Hz)