15
3-7-2. UPS Setting
At the main interface; press and hold the “up” and “down” buttons simultaneous for more than 1 second to
enter or escape from setting menu.
Two parameters to set up the UPS.
Parameter 1: For program alternatives.
Parameter 2: Option setting or values for each
program.
Available programs list for parameter 1:
Code Description
Bypass
AC
CVCF Battery
Battery Test
01 Output
voltage
Y
02
CVCF mode enable/disable
Y
03 Output
frequency
Y
04
Acceptable low voltage for bypass mode
Y
05
Acceptable high voltage for bypass mode
Y
06
Acceptable low frequency for bypass mode
Y
07
Acceptable high frequency for bypass mode
Y
08
Bypass mode forbidden/allowed
Y
09
Manual bypass mode enable/disable
Y
10
Battery backup time setting
Y
Y
Y
Y
Y
11
Hot standby function enable/disable
Y
Y
Y
Y
Y
12
Battery voltage calibration
Y Y
Y Y
Y
13
Charger voltage calibration
Y Y
Y Y
Y
14
Maximum charger current setting
Y Y
Y Y
Y
15
Battery capacity setting
Y Y
Y Y
Y
16
Battery group setting
Y Y
Y Y
Y
17
Backup time calibration
Y Y
Y Y
Y
18
Output voltage calibration
Y
Y Y
Y
*Y means that this program can be set in this mode.
01: Output voltage
Interface
Setting
Parameter 2: Output voltage
Output voltage can be chosen in parameter 2 as below:
208:
output voltage is 208Vac
220:
output voltage is 220Vac
230:
output voltage is 230Vac
240:
output voltage is 240Vac
Parameter 2
Parameter 1