16
02: Frequency Converter enable/disable
Interface
Setting
Parameter 2: Frequency mode
Setting output frequency at CVCF mode or not CVCF mode.
Two options can be chosen in parameter 2 as below:
ENA:
Setting UPS to CVCF mode.
If selected, the output frequency will be fixed at 50Hz or 60Hz
according to “
Output frequency setting
”.
The input frequency could be from 46Hz to 64Hz.
DIS:
Setting UPS to normal mode (not CVCF mode).
If selected, the output frequency will synchronize with the input
frequency within 46~54 Hz at 50Hz or within 56~64 Hz at 60Hz
according to setting in
“Output frequency setting”
.
If 50Hz is selected in
“Output frequency setting”
, UPS will
transfer to battery mode when input frequency is not within 46~54
Hz.
If 60Hz is selected in
“Output frequency setting”
, UPS will
transfer to battery mode when input frequency is not within 56~64
Hz.
03: Output frequency setting
Interface
Setting
Parameter 2: Output Frequency
50.0Hz:
output frequency is setting for 50.0Hz.
60.0Hz:
output frequency is setting for 60.0Hz.
ATO:
If selected, output frequency will be changed based on the
latest input utility frequency.
If it is within 46Hz and 54Hz, the output frequency will be 50.0Hz.
If it is within 56Hz and 64Hz, the output frequency will be 60.0Hz.
ATO is default setting.
If converter mode is enabled and output frequency is set to ATO
mode, it will display “A50” when UPS is working on 50Hz mode or
“A60” when UPS is working on 60Hz mode in LCD.
04: Acceptable low voltage for bypass
Interface
Setting
Parameter 2:
Set the acceptable low voltage for bypass.
Setting range is from 110V to 209V and the default value is 110V.
05: Acceptable high voltage for bypass mode
Interface
Setting
Parameter 2:
Set the acceptable high voltage for bypass.
Setting range is from 231V to 276V and the default value is 264V.