Fig. 3-1 Precautions of UPS Installation and Use
1
.
Place UPS on flat floor (avoid oblique and ragged floor).
2
.
Keep good ventilation, the distance of the back and side to the wall should
be above 30cm~50cm, to facilitate heat emission.
3
.
Avoid placing it in the location with sunshine, rain and dampness.
4
.
Never place it in the location with corrosive air.
5
.
Do not place articles on or around the UPS, to prevent the vent hole from
being blocked. No person is allowed to sit on it.
3.4
Selection of Cable
3.4.1
Selection of Input Air Switch
Before the input coil in of the equipment, install an air switch or a distribution
box compliant with the power and capability of the equipment, to isolate it with
commercial power. Consider especially the charge power and the current
shock, the input air switch can be higher than 1.5-2 times most current of UPS
input, which is without leakage current protection in order to avoid error action.
The distribution box should be better to be manufactured by professional
company. Please refer to Table 3-2.