1-A CONNECTION DIAGRAM 

 

1-A - The communication terminals (RS485) are located at the bottom of the inverter. And there are two 

connection terminals on the configuration circuit board:  +- terminal blocks. 

Connection steps 

 

Please unscrew the  RS485 terminal  

 

Please make the connections from the Terminal Block to TrackSo 
IoT Gateway 

 

Connect RS485 + to Pin 3 on TrackSo ( RS485+) 

 

Connect RS485 - to Pin 4 on TrackSo ( RS485-) 

 

CONFIGURATION AT THE INVERTER END 

SETTING THE BAUD RATE 

The communication baud rate is to be set at 9600 bit/s 

SETTING THE INVERTER ID 

 

The inverter ID is used to identify the inverter in a RS485 connection. Set Id of the Inverter to 

 

In case of multiple inverters start assigning Continuous numbering starting with 1, 2, 3, 4 …. (Range: 1 to 247)  

  

SETTING THE DATE & TIME 

For a precise calculation of the statistics in the inverter itself and in a monitoring system, date and time have 
to be correct.  

 

 

Valid for 10kW-SGTU-103, 12.5kW-

SGTU-1253, 15kW-SGTU-153, 17kW-

SGTU-173, 20kW-SGTU-203, SGTU-

333N 

 

With Modbus-RTU-RS485 Output 

Содержание 10kW-SGTU-103

Страница 1: ...kW SGTU 103 12 5kW SGTU 1253 15kW SGTU 153 17kW SGTU 173 20kW SGTU 203 SGTU 333N a Type A with RS485 Output b Type B with RS232 Output 2 POM SGTU 30kW POM SGTU 50kW POM SGTU 60kW RS485 For a Modbus RT...

Страница 2: ...GURATION AT THE INVERTER END SETTING THE BAUD RATE The communication baud rate is to be set at 9600 bit s SETTING THE INVERTER ID The inverter ID is used to identify the inverter in a RS485 connection...

Страница 3: ...ease make the connections from the connector RS232 of PowerOne Inv RS232 Output to TrackSo IoT Gateway as mentioned in the Table KT2 4 Please provide 12V external supply to TrackSo IoT Gateway via 12V...

Страница 4: ...ter settings SETTING THE BAUD RATE The communication baud rate is to be set at 9600 bit s Menu Setup Comm Param Baud Rate SETTING THE INVERTER ID The inverter ID is used to identify the inverter in a...

Страница 5: ...monitoring system date and time have to be correct Menu Setup System Param Time Set The above details are mentioned in the Installation Operation Manual for PowerOne Inverters Valid for 10kW SGTU 103...

Страница 6: ...the RS485 terminal as shown in A part of Figure K1 Please make the connections from the Terminal Block to TrackSo IoT Gateway as mentioned in Table P2T1 Table PT2 PowerOne RS485 connections with Track...

Страница 7: ...9200 38400 Data Bits 8 Stop Bit 1 Parity None CONFIGURATION AT THE INVERTER END Press Enter on LCD panel and get into settings menu After entering into the setup interface the system will prompt to in...

Страница 8: ...input figure confirm input and return back setup interface by pressing ENTER button press ESC button to cancel input and return back setup interface the input numerical value is between 1 and 32 Opti...

Страница 9: ...e installed location LED NAME DESCRIPTION GREEN POWER Light when Power on the device RED GSM LED Status Connection State Flashing ON for 100ms and OFF for 100ms SIM Card not found Flashing ON for 500m...

Страница 10: ...ed NC not connected PIP Connected to TrackSo Server or not CONT connected NC not connected LOG no of data points stored in devices incase of no interet 6 If the GSM light starts flashing 5 times then...

Страница 11: ...p right of the screen and click on Event Ingestion Logs in the dropdown 10 Check if there is some log generated at the time of installation of the TrackSo IoT Gateway device a If NO please restart the...

Отзывы: