background image

7

Power-Flo Pumps & Systems • 877-24PUMPS • www.powerflopumps.com

Receiving Inspection

Upon receiving the pump, it should be 

inspected for damage or shortages.   

If damage has occurred, file a claim 

immediately with the company that 

delivered the pump. If the manual is 

removed from the packaging, do not 

lose or misplace.

Storage

Any product that is stored for a period 

longer than six (6) months from the 

date of purchase should be bench 

tested prior to installation.  A bench 

test consists of,  checking the impeller 

to assure it is free turning and a run 

test to assure the motor (and switch 

if provided) operate properly.  Do not 

pump out of liquid.

Controls

Manual models require a separate 

approved pump control device or panel 

for automatic operation.  Be sure the 

electrical specification of the control 

selected properly match the electrical 

specifications of the pump.

Submergence

The pump should always be operated in 

the submerged condition.  The minimum 

sump liquid level should never be less than 

above the pump’s volute (See Figure 1).

Installation

These pumps are recommended for 
use in a sump, basin or lift station.

 

The sump, basin or lift station shall be 

sealed and vented in accordance with 

local plumbing codes. 

This pump is 

designed to pump sewage, effluent 

or wastewater, nonexplosive and 

noncorrosive liquids and shall NOT 

be installed in locations classified as 

hazardous in accordance with the 

National Electrical Code (NEC) ANSI/

NFPA 70 or Canadian Electric Code 

(CEC).

 The pump should never be 

installed in a trench, ditch, or hole with 

a dirt bottom. The legs will sink into 

the dirt and the suction will become 

plugged.

The installation should be at a sufficient 
depth to ensure that all plumbing is 
below the frost line. If this is not feasible, 
remove the check valve and size the 
basin to accommodate the additional 
backflow volume.

Pumps are most commonly installed 
in simplex or duplex stations or basins 
with a slide rail system, which allows 
the pump(s) to be installed or removed 
without requiring personnel to enter 
the station, or resting on the basin floor. 

Discharge Piping

Discharge piping should be as short 
as possible and sized no smaller than 
the pump discharge.  

Do not reduce 

the discharge pipe size below that 
which is provided on the pump.

  Both 

a check valve and a shut-off valve are 
recommended for each pump.  The 
check valve is used to prevent backflow 
into the sump.  The shut-off valve is 
used to manually stop system flow 
during pump servicing.

Liquid Level Controls

The level control(s) should be mounted 

on the discharge piping, a cable rack 

or float pole.  The level control should 

have adequate clearance so it cannot 

hang up in it’s swing and that the pump 

is completely submerged when the 

level control is in the “Off” mode.  The 

minimum tether is 3.50”. By adjusting 

the cord tether the control level can 

be changed.  One cycle of operation 

should be observed, so that any potential 

problems can be corrected.

It is recommended that the level control 

float should be set to insure that the liquid 

in the sump never drops below the top of 

the motor housing or a minimum level of 

10 inches above the basin floor.

Electrical Connections

Power cable:

The power cable mounted to the pump 

must not be modified in any way except 

for shortening to a specific application.

Any splice between the pump and the

control panel must be made in 

accordance with the electric codes. It is

recommended that a junction box, if used, 

be mounted outside the sump or be of 

at a minimum Nema 4 construction if 

located within the wet well. 

DO NOT USE 

THE POWER CABLE TO LIFT PUMP. 

Always rely upon a Certified Electrician 
for installation.

Overload Protection:
Single Phase

 - The stator in-winding

overload protector used is referred to 
as an inherent overheating protector 
and operates on the combined effect 
of temperature and current. This means 
that the overload protector will trip out 
and shut the pump off if the windings 
become too hot, or the load current 
passing through them becomes too high. 

Figure 1

Receiving & Installation

Recommended

Submergence Level

Minimum

Submergence Level

8”

Bottom of Feet

PFSE .05, .75 & 1HP 

 

 

 

 

 

 

 

 

Sewage Pumps

Содержание PFSE1044 Series

Страница 1: ...SP 1 2021 INSTALLATION SERVICE PARTS MANUAL Series PFSE51 PFSE51A PFSE51HT PFSE52 PFSE594 PFSE544 0 5 HP 1750 RPM 60 Hz Standard High Temperature Series PFSE774 PFSE794 PFSE744 0 75 HP 1750 RPM 60 Hz...

Страница 2: ...nnected Always wear eye protection when working on pumps Do not wear loose clothing that may become entangled in moving parts Pumps build up heat and pressure during operation Allow time for pumps to...

Страница 3: ...cal Oil Filled Material Carbon Ceramic Buna N POWER CORD 15 Ft Cord with Plug on 115 Volt 1 2HP 230 Volt 1 Phase Fast Disconnect Design MOTOR Oil Filled Squirrel Cage Induction Class B Insulation SING...

Страница 4: ...6 4 2 9 7 11 1 5 34 10 68 K 14 4 SOW PFSE544 0 5 460 3 60 1750 2 2 5 3 5 34 10 68 K 14 4 SOW PFSE774 0 75 200 230 1 60 1750 8 4 7 7 21 4 25 7 J 14 3 SOW PFSE794 0 75 200 230 3 60 1750 4 8 4 5 13 6 15...

Страница 5: ...5 Power Flo Pumps Systems 877 24PUMPS www powerflopumps com Performance PFSE 05 75 1HP Sewage Pumps...

Страница 6: ...ions Performance MODEL HP VOLTS PH HZ RPM FULL LOAD AMPS LOCKED ROTOR AMPS WINDING RESISTANCE MAIN START NEMA START CODE CORD SIZE CORD TYPE PFSE51HT 0 5 115 1 60 1750 11 6 21 2 E 14 3 SOOW 8 00 Disch...

Страница 7: ...o be installed or removed without requiring personnel to enter the station or resting on the basin floor Discharge Piping Discharge piping should be as short as possible and sized no smaller than the...

Страница 8: ...e pump has been properly wired lowered into the basin sump or lift station check the system by lling with liquid and allowing the pump to operate through its pumping cycle The time needed to empty the...

Страница 9: ...3 4HP 67 6 oz 1HP 74 4 oz BP Enerpar SE100 Conoco Pale Paraf n 22 Mobile D T E Oil Light Shell Canada Transformer 10 Texaco Diala Oil AX Disassembly Impeller andVolute 1 Disconnect power 2 Remove caps...

Страница 10: ...nd seal parts into seal plate 8 until bearing seats into seal plate Insert retaining ring 11 into seal plate 8 Place stator over rotor lining up motor bolts with holes in seal plate 8 Insert motor bol...

Страница 11: ...tor Lead Number Green Ground Green Black 1 White 2 Flag Terminal Capacitor Flag Terminal Capacitor Power Cable Motor Lead Number Green Ground Green 1 1 7 2 2 8 3 3 9 4 5 6 Together Power Cable Motor L...

Страница 12: ...24PUMPS www powerflopumps com Repair Parts For Repair Part Please supply Model Number and MFG Date as shown on Name Plate and Part Description and Part Number as shown on Parts List Figure 7 PFSE 05 7...

Страница 13: ...Retaining ring PF85326 12 1 Terminal block 1Ph PF103584 Terminal block 3Ph PF103583 13 1 O ring NBR STD PF2 31051 224 O ring Silicon HT PF63PFS5103 14 1 Retaining ring PF105197 15 1 Handle PF103503 16...

Страница 14: ...1 Bearing Supplied w Motor 26 1 Motor end bell Supplied w Motor 27 4 Motor screws Supplied w Motor 28 29 30 1 Motor Assy 0 5HP 115 volt 1Ph PF030369BS 0 5HP 75HP 230 volt 1Ph PF071325BS 0 5HP 75HP 23...

Страница 15: ...ase reverse any two of three power supply leads to ensure proper impeller rotation 11 Repair fixtures as required to eliminate leakage 12 Check pump temperature limits and fluid temperature 13 Replace...

Страница 16: ...been exposed to outside substances including but not limited to the following sand gravel cement mud tar hydrocarbons hydrocarbon derivatives oil gasoline solvents etc or other abrasive or corrosive...

Отзывы: