background image

7

Power-Flo Pumps & Systems • 877-24PUMPS • www.powerflopumps.com

Receiving Inspection

Upon receiving the pump, it should be 

inspected for damage or shortages.   

If damage has occurred, file a claim 

immediately with the company that 

delivered the pump. If the manual is 

removed from the packaging, do not 

lose or misplace.

Storage

Any product that is stored for a period 

longer than six (6) months from the 

date of purchase should be bench 

tested prior to installation.  A bench 

test consists of,  checking the impeller 

to assure it is free turning and a run 

test to assure the motor (and switch 

if provided) operate properly.  Do not 

pump out of liquid.

Controls

Manual models require a separate 

approved pump control device or panel 

for automatic operation.  Be sure the 

electrical specification of the control 

selected properly match the electrical 

specifications of the pump.

Submergence

The pump should always be operated in 

the submerged condition.  The minimum 

sump liquid level should never be less than 

above the pump’s volute (See Figure 1).

Installation

These pumps are recommended for 
use in a sump, basin or lift station. 

The sump, basin or lift station shall be 

sealed and vented in accordance with 

local plumbing codes. 

This pump is 

designed to pump sewage, effluent 

or wastewater, nonexplosive and 

noncorrosive liquids and shall NOT 

be installed in locations classified as 

hazardous in accordance with the 

National Electrical Code (NEC) ANSI/

NFPA 70 or Canadian Electric Code 

(CEC).

 The pump should never be 

installed in a trench, ditch, or hole with 

a dirt bottom. The legs will sink into 

the dirt and the suction will become 

plugged.

The installation should be at a sufficient 
depth to ensure that all plumbing is 
below the frost line. If this is not feasible, 
remove the check valve and size the 
basin to accommodate the additional 
backflow volume.

Pumps are most commonly installed 
in simplex or duplex stations or basins 
with a slide rail system, which allows 
the pump(s) to be installed or removed 
without requiring personnel to enter 
the station, or resting on the basin floor. 

Discharge Piping

Discharge piping should be as short 
as possible and sized no smaller than 
the pump discharge.  Do not reduce 
the discharge pipe size below that 
which is provided on the pump.
  Both 
a check valve and a shut-off valve are 
recommended for each pump.  The 
check valve is used to prevent backflow 
into the sump.  The shut-off valve is 
used to manually stop system flow 
during pump servicing.

Liquid Level Controls

The level control(s) should be mounted 
on the discharge piping, a cable rack 
or float pole.  The level control should 
have adequate clearance so it cannot 
hang up in it’s swing and that the pump 
is completely submerged when the 
level control is in the “Off” mode.  By 
adjusting the cord tether the control 
level can be changed.  One cycle of 

operation should be observed, so that any 

potential problems can be corrected.

It is recommended that the level control 

float should be set to insure that the liquid 

in the sump never drops below the top of 

the motor housing or a minimum level of 

10 inches above the basin floor.

Electrical Connections

Power cable:

The power cable mounted to the pump 

must not be modified in any way except 

for shortening to a specific application.

Any splice between the pump and the

control panel must be made in 

accordance with the electric codes. It is

recommended that a junction box, if used, 

be mounted outside the sump or be of 

at a minimum Nema 4 construction if 

located within the wet well. DO NOT USE 

THE POWER CABLE TO LIFT PUMP. 

Always rely upon a Certified Electrician 
for installation.

Overload Protection:
Single Phase
 - The stator in-winding
overload protector used is referred to 
as an inherent overheating protector 
and operates on the combined effect 
of temperature and current. This means 
that the overload protector will trip out 
and shut the pump off if the windings 
become too hot, or the load current 
passing through them becomes too high. 

Figure 1

Receiving & Installation

Recommended

Submergence Level

Minimum

Submergence Level

11”

Bottom of Feet

PF4NC-SS   

 

 

 

 

 

 

 

 

      Non-Clog Pumps

Содержание PF4NC2824SS Series

Страница 1: ...SERVICE PARTS MANUAL Series PF4NC2824SS PF4NC2834SS PF4NC2844SS PF4NC3724SS PF4NC3734SS PF4NC3744SS PF4NC3764SS PF4NC5024SS PF4NC5034SS PF4NC5044SS PF4NC5064SS 2 8 3 7 5HP 1750RPM 60Hz Submersible Non...

Страница 2: ...and discharge openings Do not insert fingers in pump with power connected Always wear eye protection when working on pumps Do not wear loose clothing that may become entangled in moving parts Pumps bu...

Страница 3: ...Filled reservoir with Secondary Exclusion seal Silicon Carbide Buna N UPPER BEARING Single row ball oil lubricated LOWER BEARING Single row ball oil lubricated POWER CORD 25 Ft Cord Epoxy sealed housi...

Страница 4: ...umps Systems 877 24PUMPS www powerflopumps com Dimensions PF4NC2824SS PF4NC3724SS PF4NC3734SS PF4NC3744SS PF4NC3764SS PF4NC5024SS PF4NC5034SS PF4NC5044SS PF4NC5064SS PF4NC2834SS PF4NC2844SS PF4NC SS N...

Страница 5: ...W 0 75 PF4NC3724SS 3 7 60 230 1 1750 A 18 5 29 0 10 3 SOW 0 69 PF4NC3734SS 3 7 60 230 3 1750 F 14 0 50 8 10 4 SOW 0 75 PF4NC3744SS 3 7 60 460 3 1750 F 7 0 25 4 10 4 SOW 0 75 PF4NC3764SS 3 7 60 208 3 1...

Страница 6: ...6 Power Flo Pumps Systems 877 24PUMPS www powerflopumps com Performance PF4NC SS Non Clog Pumps...

Страница 7: ...ws the pump s to be installed or removed without requiring personnel to enter the station or resting on the basin floor Discharge Piping Discharge piping should be as short as possible and sized no sm...

Страница 8: ...ump has been properly wired lowered into the basin sump or lift station check the system by lling with liquid and allowing the pump to operate through its pumping cycle The time needed to empty the sy...

Страница 9: ...ooling Oil Recommended Supplier Grade BP Enerpar SE100 Conoco Pale Paraf n 22 Mobile D T E Oil Light Shell Canada Transformer 10 Texaco Diala Oil AX Disassembly Impeller andVolute 1 Disconnect power 2...

Страница 10: ...otating member and not cocked or resting on bellows tail Bearing Motor 6 Slide rotor shaft with bearing 8 and seal parts 6 into seal plate 3 until bearing seats into seal plate and tighten conduit bus...

Страница 11: ...4 and gland nut 23 into motor housing 4 or conduit box cable assembly 33 and torque gland nut 23 to 15 ft lbs 19 on models PF4NC2834SS 2844SS 2854SS refill with with cooling oil and replace pipe plug...

Страница 12: ...77 24PUMPS www powerflopumps com Repair Parts For Repair Part Please supply Model Number and MFG Date as shown on Name Plate and Part Description and Part Number as shown on Parts List Figure 6 PF4NC2...

Страница 13: ...77 24PUMPS www powerflopumps com Repair Parts For Repair Part Please supply Model Number and MFG Date as shown on Name Plate and Part Description and Part Number as shown on Parts List Figure 7 PF4NC2...

Страница 14: ...F92010083 19 1 O ring PF92010082 20 1 Pipe Plug 3 4 NPT 21 1 Eye Bolt 1 2 13 x 1 Lg Power Cable Assy Includes 22 23 24 25 PF053165 22 1 Power Cable 25 Ft 10 4 SOW PF31030003 23 1 Gland Nut PF30400903...

Страница 15: ...werflopumps com Repair Parts For Repair Part Please supply Model Number and MFG Date as shown on Name Plate and Part Description and Part Number as shown on Parts List Figure 8 PF4NC2824SS 3724SS 3734...

Страница 16: ...24PUMPS www powerflopumps com Parts List For Repair Part Please supply Model Number and MFG Date as shown on Name Plate and Part Description and Part Number as shown on Parts List Figure 9 PF4NC2824S...

Страница 17: ...1 V Gasket PF92010112 17 2 Soc Hd Cap Screw 1 4 20 x 1 Lg Stainless 18 1 O ring PF92010083 19 1 O ring PF92010082 20 1 Pipe Plug 3 4 NPT 21 1 Eye Bolt 1 2 13 x 1 Lg Power Cable Assy Includes 22 23 24...

Страница 18: ...w powerflopumps com Parts List For Repair Part Please supply Model Number and MFG Date as shown on Name Plate and Part Description and Part Number as shown on Parts List Figure 10 PF4NC3734SS 3744SS 3...

Страница 19: ...F91010111 15 1 Washer Impeller PF91010051 16 1 V Gasket PF92010112 17 2 Soc Hd Cap Screw 1 4 20 x 1 Lg Stainless 18 1 O ring PF92010083 19 1 O ring PF92010082 20 1 Pipe Plug 3 4 NPT 21 1 Eye Bolt 1 2...

Страница 20: ...On Part Numbers 33 1 Conduit Box PF03100010 35 1 O ring PF92010063 36 4 Cap screw 1 4 20 x 1 Lg Stainless 37 4 Lockwasher 1 4 Stainless 38 6 Female Connector PF94010041 39 1 85gal Cooling Oil Aquire l...

Страница 21: ...21 Power Flo Pumps Systems 877 24PUMPS www powerflopumps com Notes PF4NC SS Non Clog Pumps...

Страница 22: ...22 Power Flo Pumps Systems 877 24PUMPS www powerflopumps com Notes PF4NC SS Non Clog Pumps...

Страница 23: ...phase reverse any two of three power supply leads to ensure proper impeller rotation 11 Repair fixtures as required to eliminate leakage 12 Check pump temperature limits and fluid temperature 13 Repla...

Страница 24: ...not been installed operated or maintained in accordance with Manufacturer s installation instructions that has been exposed to outside substances including but not limited to the following sand grave...

Отзывы: