background image

25.  Turn the burner on and let it advance to the main flame  

 

light off position, taking action as necessary to hold  

 

the linkage at the low fire position by using a manual  

 

potentiometer or electrically disconnecting the    

 

modulating motor. Power Flame burners are test fired  

 

at the factory, and linkage adjustments for modulation  

 

are made at that time. Note that the factory settings  

 

relate to good operation while firing into open test pits,  

 

and will therefore not normally relate directly to the  

 

absolute fuel/air ratios while firing under specific field  

 

conditions. It is suggested that the factory settings be  

 

noted and marked on the linkage prior to proceeding  

 

with final adjustment. This will allow a return to those  

 

settings as initial reference points, if need be.

26.  On internal bypass nozzle systems, oil pressure at the  

 

pump nozzle port will generally be between 270 and  

 

300 psig from low to high fire. At certain input ranges  

 

of burner models C4 and C5, nozzle pressure may fall  

 

off to approximately 240 psig when in the low fire   

 

position. For oil pressure settings on simplex nozzle  

 

systems, refer to page 34, Table 9.

27.  On internal bypass nozzle systems, typical low fire  

 

nozzle bypass line pressures will generally be in the  

 

area of 60 to 90 psig. High fire nozzle bypass line  

 

pressures will generally be in the range of 200 to 225  

 

psig, but these pressures can vary, depending upon the  

 

nozzle selected for a particular firing application. Refer  

 

to page 31, Table 8 for specific nozzle bypass line  

 

pressures. Refer to page 34, Table 9 for simplex nozzle  

 

systems and pressures.

28.  With the burner in the factory set low fire position,  
 

adjust air and fuel linkage to good fuel/air ratio low fire  

 

settings (8 - 10% CO

2

 and #0 - #2 smoke reading).  

 

Mark the linkage at the new settings.

29.  Increase the firing rate to the midway point. Set the  
 

fuel/air ratios to achieve good combustion values (9 - 

 

11% CO

2

 and #0 to #2 smoke reading). Mark the 

 

linkage as a reference point for this new mid-fire 

 position.
30.  Increase the rate to the high fire position and repeat the  

 

tests done for the mid-point adjustment. Results should  

 

be in the area of 12

1

/

2

% CO

2

 and no more than #2  

 

smoke. The metering device setting and air damper  

 

openings should be marked and noted to obtain the  

 

high fire reference points.

31.  Operate the modulating lever arm on the modulating  

 

motor through the three previously determined reference  

 

points. Minor setting modifications may be required to  

 

ensure that the reference points are acquired.

32.  Tighten (finger tight) the hex bolt to the linkage rod at  

 

the swivel on the modulating motor driver arms, and  

 

run the motor through its full travel to ensure that  

 

linkage is free and that the limits on the metering 

 

device and air dampers are not exceeded.

33.  Intermittently operate the burner until the water is   

 

warm in the boiler, or follow specific initial firing  

 

recommendations provided by the heat exchanger  

 manufacturer.

34. Tighten all linkages and permanently mark settings.

35.  Limit control check should be made as follows:
 

A)  Permit the burner to run until the limit control  

 

    settings have been reached.

 

B)   The burner should turn off when the set temperature  

 

    or pressure has been reached. If the burner is Low/ 

 

    High/Low or Modulating, set the controls so that the  

 

    burner will go to the low fire position before the  

 

    operating limit control turns the burner off.

 

C)  After the differential pressure or temperature  

 

    drop, the burner should start automatically.

 

D)  With the unit running normally, open the  

 

 

    blowdown valve and remove water to the point  

 

    below the low water cutoff setting. The burner  

 

    should turn off and restart automatically when  

 

    the proper water level is re-established. (If manual  

 

    reset type low water cutoff is used, it will have  

 

    to be reset.)

 

E)   Set and check operation of:

 

    (1)  Low Oil Pressure Switch (if supplied). Set  

 

     

at 80% of low fire oil pressure. Check visually,  

 

     

or test electrically to confirm that circuit    

 

     

opens at the proper oil pressure.

 

    (2)  Blower Combustion Air Flow Switch (if   

       supplied).
 

     

(a)  Shut burner power off.

 

     

(b)  Disconnect both wires at the air flow  

 

     

    switch and temporarily clip them  

 

 

     

    together. Make sure that they cannot  

 

     

    ground against anything, since they  

 

     

    will be powered with 110 volts during  

         the 

test.

 

     

(c)  Put a continuity meter across the two  

         terminals.
 

     

(d)  Disconnect the wire to the main   

 

     

    automatic oil valve.

 

     

(e)  Start the blower motor. The meter   

 

     

    should read electrical continuity as soon  

 

     

    as the blower starts.

 

     

(f)   Disconnect the blower motor lead wire,  

 

     

    or open the main power disconnect   

 

     

    switch to the burner. Within 4 to 5    

 

     

    seconds after the blower motor is de- 

 

     

    energized, the meter should indicate an  

 

     

    open air flow switch circuit (no continuity).

 

     

(g)  If the switch does not open in 4 to 5   

 

     

    seconds, readjust accordingly. Turn the  

 

     

    air flow switch adjustment screw  

 

 

     

    clockwise to shorten cut-off response  

 

     

    time, and counter-clockwise to lengthen  

 

     

    cut-off response time.

 

     

(h)  Turn the burner power off. Remove the  

 

     

    shorting clip from the two disconnected  

 

     

    wires and let them hang loose. (They  

 

     

    will be powered with 110 volts, so do  

 

     

    not let them ground out.)

 

     

(i)   Reconnect the wire to the main  

 

 

     

    automatic oil valve. Turn the burner on.  

 

     

    With the air flow switch wires discon- 

 

     

    nected, the burner should go into a   

 

     

    purge cycle, but neither the ignition nor  

 

     

    the main fuel valve circuits will be    

 

     

    energized. If they do energize, there is  

 

     

    a wiring problem. Correct as required.

 

     

(j)     Turn power off. Reconnect the air flow  

 

     

    switch wires to the air flow switch    

 

     

    terminals. Place burner back into    

         normal 

operation.

 

    (3)  All burner and heat exchanger controls and  

 

     

operating devices.

36. The Owner’s Operating Instructions, page 51 of this  

 

manual, should be posted in a clearly visible location  

 

close to the burner.

37.  If the burner operation is abnormal, refer to Section  

 7 

Trouble Shooting Suggestions, as well as trouble  

 

shooting information in the flame safeguard 

C30

Rev.709

Содержание C1-GO-10

Страница 1: ...C MANUAL POWER FLAME INCORPORATED...

Страница 2: ...6 Removable Total Access Door 27 Optional Board for Sequence Indicator Lights The computer generated Burner Specification Sheets shipped with the burner represent the as built version of your specific...

Страница 3: ...fore starting up the system all appropriate air and oil leak tests should be performed Make certain that the tank atmospheric vent line is unobstructed Refer to page 12 Figure 11 for fuel pump oil pip...

Страница 4: ...valves etc Suction line vacuum values for such compo nents vary by manufacturer A Rule of Thumb to determine total vacuum for suction line sizing is to add 10 to vacuum determined from Figure 10 calcu...

Страница 5: ...r calls for low fire the normally closed Oil Solenoid Return Valve 7 closed at high fire is energized reducing nozzle pressure to the low fire rate Simultaneously the Three Way Solenoid Valve 10 is de...

Страница 6: ...trol Mode Using a Two Step Oil Pump Model C O Field Piped Check Valve At Tank Fuel Shutoff Valve Fusible Link Valve If Required by Code Check Valve Field Piped 12 pressure setting of the pump low fire...

Страница 7: ...urn Pressure Tap 8 5 Metering Valve 7 1 8 Allen Screw For Oil Nozzle Pressure Adjustment Under Cap Vacuum Gauge Inlet Port Optional Return Port For Simplex Nozzle Use Alternate Connec tion to Tee on O...

Страница 8: ...us tion chambers or high heat release pressurized fireboxes Moving the adjustment knob back increases the premix air Gas Oil Linkage Adjustment For Full Modulation Standard System Typical general link...

Страница 9: ...als is for factory use only and should not be used for incoming power connections 2 Close main and checking gas cocks Open suction line manual oil valves and others as appropriate 3 Tighten all screws...

Страница 10: ...uit the particular operating conditions 3 Do not secure flame safeguard control into its wiring base until it has been determined that there are no shorts or grounds in the system 4 Install oil pressu...

Страница 11: ...chamber 18 For small On Off burners with a simplex nozzle adjustments consist primarily of attaining correct fuel air ratios Adjustments should be set to obtain11 121 2 CO2 and no more than a 2 smoke...

Страница 12: ...rm in the boiler or follow specific initial firing recommendations provided by the heat exchanger manufacturer 34 Tighten all linkages and permanently mark settings 35 Limit control check should be ma...

Страница 13: ...sure gauges overhead oil lines or fittings A leaking check valve on the bypass return line from the nozzle can create the same effect 6 The Teflon seal should stay on the nozzle when servicing On some...

Страница 14: ...2 Fuel Oil By Pass Return Closed Approx High Fire Rate GPH 300 PSIG By Pass Return Closed Approx High Fire By Pass Return Pressure PSIG By Pass Return Closed Approx By Pass Return Pressure PSIG Appro...

Страница 15: ...eturn and Firing Rates Will be Reduced Somewhat Consult Factory for Further Information When Supply Pressure to Nozzle is Lower Than 300 PSIG the By Pass Return and Firing Rates Will be Reduced Somewh...

Страница 16: ...lon seal in the Monarch F80BPS and Delavan 33769 nozzles is an integral part of the nozzles and that if the seal is removed accidentally the nozzle must be replaced On the Delavan 30630 and 30637 nozz...

Страница 17: ...ulators should be kept clean and must be replaced if cracked 2 The spark gap must be set in accordance with the dimensions noted Refer to Figures 30 31 32 Ensure that the distance between the electrod...

Страница 18: ...Setting 1 16 Blade Tips After Adj Must be Within 1 16 of A Flat Plane Mark Pipe With Saw For Full Forward Pilot Extends Thru Diffuser 0 125 1 8 5 32 Diameter Orifice Gas Inlet Oil Nozzle Choke Assembl...

Страница 19: ...e or check valve not holding Correct as required GAS OPERATION 1 Burner Motor Runs but Pilot Does Not Light A Gas supply to burner shut off make sure all manual gas supply valves are open Automatic hi...

Страница 20: ...echanical binding of linkage Readjust linkage O Loose wiring connections Check and tighten all connections 2 Oil Flame Ignites but then Flame Safeguard Control Locks Out on Safety A Flame scanner lens...

Страница 21: ...f necessary F On two step pump N O pump mounted oil solenoid valve defective not closing Replace valve or pump G Oil pump coupling loose slipping or defective Replace H Linkage mechanically binding Re...

Страница 22: ...turer s instructions Refractory hold in As required annually Service Technician See Pilot turndown tests High limit safety control Annually Service Technician Refer to heat exchanger manufacturer s in...

Отзывы: