POWER ELECTRONICS
SD700
FAULT MESSAGES. DESCRIPTIONS AND ACTIONS
45
4.2.2.
Visualization Parameters
Parameter Screen
Description
Address
Modbus Range
SV5.13
PMP manSP=+0.0%
LOCAL manual speed reference.
42042
-20480 to 20480
SV5.14
PMP MRe1=0.0%
Local setpoint 1 of PID. Multi-reference 1.
42151
0 to 32760
SV5.15
PMP MRe2=0.0%
Local setpoint 2 of PID. Multi-reference 2.
42152
0 to 32760
SV5.16
PMP MRe3=0.0%
Local setpoint 3 of PID. Multi-reference 3.
42153
0 to 32760
SV5.17
PMP MRe4=0.0%
Local setpoint 4 of PID. Multi-reference 4.
42154
0 to 32760
SV5.18
PMP MRe5=0.0%
Local setpoint 5 of PID. Multi-reference 5.
42155
0 to 32760
SV5.19
PMP MRe6=0.0%
Local setpoint 6 of PID. Multi-reference 6.
42156
0 to 32760
SV5.20
PMP MRe7=0.0%
Local setpoint 7 of PID. Multi-reference 7.
42157
0 to 32760
SV5.21
PMP MRe8=0.0%
Local setpoint 8 of PID. Multi-reference 8.
42158
0 to 32760
SV5.22
T AutOFF=OFF
Time for Automatic Stop.
42044
0 to 999
SV5.23
TIME OFF=OFF
It shows the resting time in minutes for the
automatic stopping of the system.
42356
0 to 6000
SV5.24
MAX flow=1000l/s
Level of maximum flow.
42143
0 to 32760
SV5.25
RESET LEVL=+100%
Reset level for the flow control algorithm.
42145
0 to 100
SV5.26
SLEP FLO=0.0l/s
Flow level to sleep the drive.
42324
0 to 32760
SV8.1
R=0.0Bar
0.0Bar
PID setpoint value and feedback value.
42007
PID Ref
42009
Feedbk
Real value = (Modbus value / 10)
SV8.2
REGL +0.0% +0.0%
Drive status during pump control operation.
42002
Status
42006
PID Ref
42008
Feedbk
0 to 22
SV8.3
1OFF 2OFF 3OFF Status of the fixed pumps 1-3.
42003
FP1
42004
FP2
42005
FP3
0
OFF
1
RDY
2
ON
3
FLT
SV8.4
4OFF 5OFF
Status of the fixed pumps 4-5.
42022
FP4
42023
FP5
0
OFF
1
RDY
2
ON
3
FLT
SV8.5
Flow = 0.0l/s
Present value read by the analogue input or
pulse input where the sensor is connected.
42142
Real value = (Modbus value / 10)
SV8.6
STATUS PUMP
PROGRAM
In the visualization lines of the display,
messages will be displayed according to the
present status of pump program.
42002
0 to 22
Содержание SD700 Series
Страница 1: ...Variable Speed Drive Application Manual PUMPS...
Страница 2: ......
Страница 3: ...Variable Speed Drive Application Manual PUMPS Edition March 2011 SD70MTAP01BI Rev B...
Страница 4: ...SD700 POWER ELECTRONICS 2...
Страница 8: ...SD700 POWER ELECTRONICS 6 INDEX...
Страница 61: ......
Страница 63: ...www power electronics com...