POWER ELECTRONICS
SD700
DESCRIPTION OF PROGRAMMING PARAMETERS
37
3.6.15.
Subgroup 25.9 – S25.9: Fixed Pumps Control
Parameter
Name /
Description
Range
Function
Set on
RUN
1 ENABLE PUMP1=N
G25.9.1
/ To
enable fixed pump
associated to
output relay 1
N
Y
When activating pump control the relay 1 is configured to '28 PUMP
CNTRL', to control fixed pumps. If the pump 1 associated to this relay is
not needed, we recommend you disable it from here. In this way, the
relay can be configured for other uses.
OPT.
FUNCTION
N=NO
To disable the fixed pump associated to the relay
1.
Y=YES
To enable the fixed pump associated to the relay
1. The relay is programmed to '28 PUMP CNTRL'
and free-configuration is not allowed for it.
YES
2 ENABLE PUMP2=N
G25.9.2
/ To
enable fixed pump
associated to
output relay 2
N
Y
When activating pump control the relay 2 is configured to '28 PUMP
CNTRL', to control fixed pumps. If the pump 2 associated to this relay is
not needed, we recommend you disable it from here. In this way, the
relay can be configured for other uses.
OPT.
FUNCTION
N=NO
To disable the fixed pump associated to the relay
2.
Y=YES
To enable the fixed pump associated to the relay 2.
The relay is programmed to '28 PUMP CNTRL' and
free-configuration is not allowed for it.
YES
3 ENABLE PUMP3 =N
G25.9.3
/ To
enable fixed pump
associated to
output relay 3
N
Y
When activating pump control the relay 3 is configured to '28 PUMP
CNTRL', to control fixed pumps. If the pump 3 associated to this relay is
not needed, we recommend you disable it from here. In this way, the
relay can be configured for other uses.
OPT.
FUNCTION
N=NO
To disable the fixed pump associated to the relay
3.
Y=YES
To enable the fixed pump associated to the relay
3. The relay is programmed to '28 PUMP CNTRL'
and free-configuration is not allowed for it.
YES
4 ENABLE PUMP4=N
G25.9.4
/ To
enable fixed pump
associated to
analogue output 1
N
Y
When activating pump control and selecting digital input as ‟55 FIX
PUMP4 FLT‟, and after enabling this parameter, the analogue output 1 is
configured to '27 MACRO PUMP', to control fixed pumps. If the pump 4
associated to this analogue output is not needed, we recommend you
disable it from here.
In this way, the analogue output can be configured for other uses.
OPT.
FUNCTION
N=NO
To disable the fixed pump associated to the relay
4.
Y=YES
To enable the fixed pump associated to the
Analogue Output 1. AO1 is programmed to '27
MACRO PUMP' and free-configuration is not
allowed for it.
YES
5 ENABLE PUMP5=N
G25.9.5
/ To
enable fixed pump
associated to
analogue output 2
N
Y
When activating pump control and selecting digital input as ‟56 FIX
PUMP5 FLT‟, and after enabling this parameter, the analogue output 2 is
configured to '27 MACRO PUMP', to control fixed pumps. If the pump 5
associated to this analogue output is not needed, we recommend you
disable it from here.
In this way, the analogue output can be configured for other uses.
OPT.
FUNCTION
N=NO
To disable the fixed pump associated to the relay
5.
Y=YES
To enable the fixed pump associated to the
Analogue Output 2. AO2 is programmed to '27
MACRO PUMP' and free-configuration is not
allowed for it.
YES
Содержание SD700 Series
Страница 1: ...Variable Speed Drive Application Manual PUMPS...
Страница 2: ......
Страница 3: ...Variable Speed Drive Application Manual PUMPS Edition March 2011 SD70MTAP01BI Rev B...
Страница 4: ...SD700 POWER ELECTRONICS 2...
Страница 8: ...SD700 POWER ELECTRONICS 6 INDEX...
Страница 61: ......
Страница 63: ...www power electronics com...