POWER ELECTRONICS
SD700
DESCRIPTION OF PROGRAMMING PARAMETERS
27
Parameter
Name /
Description
Range
Function
Set on
RUN
5 SETPT1=0.0Bar
LOCAL SETPOINT 1
G25.1.5
/ Local
setpoint 1 for PID
0 – 3276
Engineering
Units
In case of operation with only one local setpoint for PID, the value will be
the set value in G25.1.5.
The applied speed in each case will depend on the activation status of
the digital inputs configured as options ‟63 SETPONT PIN1‟, ‟64
SETPONT PIN2‟ and ‟65 SETPONT PIN3‟.
The assigned speed will be done according to the attached table:
DIGITAL INPUTS
PID SETPOINTS
DI(z)=65
DI(y)=64
DI(x)=63
0
0
0
G25.1.5 „SETPT1‟
0
0
X
G25.1.6 „SETPT2‟
0
X
0
G25.1.7 „SETPT3‟
0
X
X
G25.1.8 „SETPT4‟
X
0
0
G25.1.9 „SETPT5‟
X
0
X
G25.1.10 „SETPT6‟
X
X
0
G25.1.11 „SETPT7‟
X
X
X
G25.1.12 „SETPT8‟
Note
: It is possible to operate with the following units %, l/s, m/s, l/min,
m³/min, l/h, m³/h, m/s, m/min, m/h, Bar, KPa, Psi, m, ºC, ºF, ºK, Hz, rpm.
It depends on the units of the sensor used.
YES
6 SETPT2=0.0Bar
LOCAL SETPOINT 2
G25.1.6
/ Local
setpoint 2 for PID
YES
7 SETPT3=0.0Bar
LOCAL SETPOINT 3
G25.1.7
/ Local
setpoint 3 for PID
YES
8 SETPT4=0.0Bar
LOCAL SETPOINT 4
G25.1.8
/ Local
setpoint 4 for PID
YES
9 SETPT5=0.0Bar
LOCAL SETPOINT 5
G25.1.9
/ Local
setpoint 5 for PID
YES
10 SETPT6=0.0Bar
LOCAL SETPOINT 6
G25.1.10
/ Local
setpoint 6 for PID
YES
11 SETPT7=0.0Bar
LOCAL SETPOINT 7
G25.1.11
/ Local
setpoint 7 for PID
YES
12 SETPT8=0.0Bar
LOCAL SETPOINT 8
G25.1.12
/ Local
setpoint 8 for PID
YES
13 T AutOFF=OFF
AUTO-OFF DELAY
G25.1.13
/ Time
for automatic stop
OFF,
0.1 – 99.9h
User can set a run time that once elapsed the drive will stop
automatically. When set this time value starts to elapse immediately and
the drive will stop once this time has expired. At that moment the
parameter value becomes OFF and the status of the program will change
to „COMPLETED‟. If you want to the drive to stop automatically again,
you must reset the stop time.
There are two visualization parameters related with this parameter:
„SV5.22 T AutOFF= OFF‟ it is directly the G25.1.13, translated to the
visualization group SV5.
„SV5.23 TIME OFF= OFF‟ that shows the remaining time in minutes for
the automatic stop of the system.
YES
14 Comms Cntrol= N
G25.1.14
/
Communications
Control
Y
N
In order to be capable of starting and stopping the drive from
communications. Either via field bus or GSM-Modem (with graphic
display).
. YES
Содержание SD700 Series
Страница 1: ...Variable Speed Drive Application Manual PUMPS...
Страница 2: ......
Страница 3: ...Variable Speed Drive Application Manual PUMPS Edition March 2011 SD70MTAP01BI Rev B...
Страница 4: ...SD700 POWER ELECTRONICS 2...
Страница 8: ...SD700 POWER ELECTRONICS 6 INDEX...
Страница 61: ......
Страница 63: ...www power electronics com...