Operating Procedures
01.4IB.65090A
8. Disconnect the control box power cord
from the ground and test device
.
9. Rotate key KCF in key lock K1 to electrically
lock the ground and test device in the
“CLOSED” position. Key KCF is now captive
and key KB is released
.
10. Transfer key KB to key lock K4
.
Rotate key KB, electrically and mechanically
locking the ground and test device in the
“CLOSED” position. Key KB is now captive
and key KD is released.
11. Transfer key KD to key lock K5
Rotate the KD key to unlock the test port
shutters. Key KD is now captive.
12. Open the test port shutters using the slide
. With the test ports
fully open, the K5 interlock is blocked from
operating and the key remains captive.
13. Remove the test probes
from the
test ports. Close the test port shutters.
14. Rotate key KD to lock the test port shutter.
Key KD is now released.
15. Transfer key KD to key lock K4. Rotate key
KD. Key KD is now captive and key KB is
released.
16. Transfer key KB to key lock K1 and rotate
the key. The ground and test device control
circuit is now enabled. Key KB is now
captive and key KCF is released.
17. Verify that the control selector switch on
the front of the ground and test device is in
the “OFF” (center) position
.
18. Connect the power cord of the remote
control box to the ground and test device
. Ensure the cord is locked into
the connected position by turning the plug
clockwise.
19. Move the control selector switch from the
“OFF” position to the “OPEN” position
.
20. Turn the remote control box “ON”
and depress the “OPEN”
pushbutton
on the remote
control box to open the ground and test
device.
21. Move the control selector switch to the
“OFF” position
and turn the
remote control box “OFF”
.
22. Disconnect the remote control box power
cord from the ground and test device
23. Rotate key KCF in key lock K1
. The ground and test device is
now electrically disabled. The KCF key is
now captive and key KB is now removable.
24. Disconnect the secondary disconnect plug
from the ground and test device secondary
disconnect receptacle
25. Transfer key KB to key lock K2
and rotate key KB. The ground and test
device is now mechanically locked in the
“OPEN” position. The KB key is now captive
and key KC is removable
26. Transfer key KC to key lock K3
and rotate the key. Key KC is now captive.
The ground and test device racking access
shaft is now accessible.
27. Insert the racking handle and rotate
the handle counterclockwise to move
the ground and test device into the
“Disconnected” position. The racking
handle is also equipped with an input
torque limiter that will indicate limit to
the operator by a mechanical ratcheting
mechanism for positive operator feedback.
Remove the racking handle.
28. Rotate key KC to lock the ground and test
device in the “Disconnected” position. Key
KC is now released.
29. Transfer key KC to key lock K2
and rotate key KC. Key KC is now captive
and key KB is now released.
30. Transfer key KB to key lock K1
and rotate key KB. Key KB is
now captive and the KCF key is released.
31. Remove the ground and test device from
the compartment.
32. Remove key KCF from key lock K1
33. Secure key KCF in a lock box on premises.