5
Safety
01.4IB.65090A
6. Do not attempt to force or bypass any
interlocks. The interlocks are furnished
for the safety of the operator and the
protection of the equipment being tested
and the test device.
Forcing or bypassing the interlocks can result
in a condition dangerous to the operator
and/or damaging to the equipment.
!
CAUTION
7. Do not attempt to service the device while
it is installed in a switchgear compartment
or on a lift truck. For service, the device
must be located either on the floor or on a
sturdy, level work bench, and blocked from
rolling.
8. For service, the device must be in the OPEN
position and all operating springs must
be discharged. These conditions should
be verified before removing any covers or
attempting any service.
9. Store the electrically operated ground and
test device in a clean, dry area free from
dust, dirt, moisture, caustic atmosphere,
and vermin.
10. Keep all insulating surfaces, which include
primary support insulation and insulation
barriers, clean and dry.
11. Check all primary circuit connections to
make certain that they are clean and tight.
12. Take extreme care while using this device to
avoid contacting “live” or “hot” (energized)
terminals.
e. S
Afety
l
ABelS
The equipment described in this document
has
DANGER
,
WARNING, CAUTION,
and
instruction labels attached to various locations.
All equipment
DANGER
,
WARNING,
CAUTION,
and instruction
labels shall be observed
when the ground and test device is handled,
operated, or maintained.
Warning and Caution labels are located in
various places. Do NOT remove or deface any
of these warning/caution labels.
NOTICE