10. INSTALLING THE FLUES
The boiler is easy and flexible to install thanks to the extensive range of available acces-
sories, as described below. The boiler has been designed for connection to a vertical or
horizontal concentric flue.
WARNINGS
C13, C33
The terminals for separate flues must be fitted in accordance with the BS stan-
dard and the Clean Air Act 1993. Detailed instructions are provided with the individual
accessories.
For optimal installation, the accessories supplied by the manufacturer should
be used.
TABLE 1A
If the flue and air ducts installed are not supply by POTTERTON
COMMERCIAL, make sure they are certitied for the type of use and
have a maximum pressure drop as indicated in the table to the side.
∆P (Pa)
WH 90
320
WH 110
370
To optimise operating safety, make sure the flues are firmly fixed to the wall with suitable brackets for every 1 metre of flue..
Make sure there is a minimum downward slope of 5 cm per metre of duct towards the boiler.
SOME OUTLET FLUE INSTALLATION EXAMPLES AND THEIR RELATIVE MAXIMUM LENGTHS ARE SHOWN IN ANNEX
“SEC-
TION” D
AT THE END OF THIS MANUAL.
10.1 CONCENTRIC FLUES
This type of flue is used to discharge exhaust fumes and draw
combustion air both outside the building. The 87° concentric
bend allows the boiler to be connected to a flue-air in any di-
rection as it can be rotated by 360° It can also be used as a
supplementary curve combined with a concentric flue or a 45°
bend.
If fumes are discharged outside the building, the flue-air must
protrude at least 200 mm from the wall to allow an aluminium
weathering surround to be fitted and sealed to avoid water in-
filtrations.
•
The 87° bend reduces the total flue length by 1 metre.
•
The 45° bend reduces the total flue length by 0.5 me-
tres.
•
The first 87° bend is not included when calculating the maximum available length.
10.2 CASCADE FLUES
This type of flue evacuates the products of combustion of more than one boiler in a cascade connection through a shared flue
header. The header may only be used to connect the boilers to the flue.
BOILER
MODEL
MAXIMUM NUMBER OF BOILERS
IN A CASCADE CONNECTION
PARAMETER P60(a)
Minimum power rpm
Ø160 mm
(250 kW Max)
Ø200 mm
(500 kW Max)
G20
G31
WH 90
2
5
1450
1650
WH 110
2
4
1500
1500
In this outlet typology, a flue no-return valve, Ø 80/110 mm, must be fitted to each boiler. Change the parameter P60(a) as
shown in table following the procedure described in chapter 14.
The flue header size must be calculated by a qualified technician during the system design stage, as required by current regu-
lations.
Содержание Sirius two WH
Страница 21: ...21 I N S T A L L E R S e c t i o n e n 7108686 02 1 11 12 ...
Страница 25: ...25 S E C T I O N C 7108686 02 1 11 12 ...
Страница 28: ...7108686 02 1 11 12 28 S E C T I O N F WEATHER COMPENSATION CURVE GRAPHS QAC34 ...
Страница 29: ...29 S E C T I O N G 7108686 02 1 11 12 AGU 2 550 CR_0349 CR_0349 AVS 75 ...
Страница 30: ...7108686 02 1 11 12 30 S E C T I O N G CG_2482 SAFETY THERMOSTAT Tmax 50 C free contact ...
Страница 31: ...31 7108686 02 1 11 12 MODIFIED PARAMETERS Nr VALUE NOTE ...