Caution
Connect the condensate discharge to the waste water near the
boiler.
5.3.1
Ventilation
To allow the intake of combustion air, sufficient ventilation must be
provided in the boiler room, for which the cross section and position must
satisfy the regulations in force in the country in which the boiler is installed:
BS 5440 Part 1 and Part 2:
For boilers with a nominal output of more than 70 kW: Upper and lower
air vents compulsory
BS 6644 and IGEM/UP-10
If the boiler is installed in closed premises, respect the minimum
dimensions given in the diagram below. Also allow for openings to obviate
the following hazards:
Accumulation of gas
Overheating of the premises
Minimum cross section of openings: see BS 5440 Part 1 and Part 2, and
BS 6644.
Ventilation to be provided for the boilers
Ventilation to be provided for boilers with low-loss header
(optional)
5.3.2
Overall space needed for the boiler
To ensure adequate access to the appliance and facilitate maintenance,
allow sufficient space around the boiler, according to the information
provided.
Fig.19
Ventilation to be provided for the
boilers
MW-3000011-01
Fig.20
Ventilation to be provided for boilers
with low-loss header (optional)
MW-3000012-01