Parameter number
Parameter
Description
Unit
Factory set
ting
Heating
circuit 1
Heating
circuit 2
Heating
circuit 3
742
1042
1342
Flow temp setpoint
room stat
The set flow value is applied in room tempera
ture thermostat mode. ‘ ---‘ the boiler is running
in modulation mode.
°C
80
750
1050
1350
Room influence
Influence of the room temperature and the
outside temperature on calculating the flow
temperature: ---%: Simple regulation in ac
cordance with outside weather conditions:
1…99%: Regulation in accordance with out
side weather conditions with room tempera
ture influence.
100%: Regulation in accordance with the
room temperature only.
%
50
760
1060
1360
Room temp
limitation
Cuts the circulating pump if the room tempera
ture exceeds the current set point + parameter
760, 1060, 1360.
°C
0.5
809
1109
1409
Continuous pump
operation
No : The heating circuit / boiler pump may be
shut down during an accelerated decline in
temperature or when the room temperature
set point is reached.
Yes : The heating circuit / boiler pump also
continues to run during the accelerated de
cline in temperature and when the room tem
perature set point is reached.
–
no
834
1134
1434
Actuator running
time
Setting the stroke of the servomotor on the
mixing valve used
seconds 30
850
1150
1450
Floor curing
function
Controlled screed-drying function:
Off : The function is inoperative.
Curing/functional heating : Active for 7 days,
3 days at 25°C and 4 days at 55°C.
Curing heating : Active for 18 days, 6 days
from 25°C to 55°C increasing by 5°C a day,
6 days at 55°C, 6 days from 55°C to 25°C di
minishing by 5°C a day.
Functional/curing heating : "Functional Heat
ing" cycle first, and then "Ready for Occupa
tion".
Manually : Regulation is based on the "Man
ual Control Drying" set point.
S
Off
851
1151
1451
Floor curing setp
manually
The flow temperature set point of the "Manual"
controlled drying function can be set separately
for each heating circuit.
°C
25
855
1155
1455
Floor curing setp
current
Displays the current day of the controlled
screed-drying function. With ‘ ---‘ the function is
deactivated.
-
‘---’
856
1156
1456
Days
complete.current
Displays the current flow temperature set point
of the controlled screed-drying function. With
‘---‘ the function is deactivated.
-
‘---’
Tab.56 Menu Temps / mode hot water
Parameter
number
Parameter
Description
Factory setting
1600
Operating mode
Off: Permanent running at the frost-protection set point.
On : Domestic hot water loading is done automatically at the
nominal set point.
Eco : The temperature maintenance function is deactivated.
On
1610
Hot water temp
setpoint
DHW set point during release times
60°C
9 Settings
74