2.4 Condensate Drain Pipe
Before fitting, fill the condensate trap with water.
Fit the steady brac
k
et (with round hole) for the
condensate trap to the lower pair of holes in the left hand
cylinder side panel. Snap the
C
-shaped brac
k
et into the
groove in the condensate connector. Insert the
condensate trap into the steady brac
k
et and fit the
C
-
shaped brac
k
et to the upper pair of holes in the left hand
cylinder side panel.
Ensure that the washer seal is in place as indicated and
tighten the large nut.
The condensate pipe should be run in 2
1
.
5
/22.0 mm
diameter plastic material suitable for operation at 60°
C
.
Solvent weld
P
V
C
overflow is recommended or a
PP
system can be used.
C
opper tube must not be used. Do
not use push-fit plastic pipe.
Use the flexible pipe provided to connect to 2
1
.
5
mm
P
V
C
pipe; alternatively a Marley or
P
lumb
C
enter elbow can
be used to direct the condensate pipe through the
L
H
side panel (see Fig.
1
0a). When using the Osma
P
V
C
overflow system, a 3/4 -to-22mm adaptor No.
158
may be
required.
Internal pipewor
k
should have a bore diameter no smaller
than
1
4 mm.
External pipewor
k
should be
k
ept to a minimum, and
have a bore diameter no smaller than 32 mm.
Ideally the condensate pipe should be run internally to
the house soil and vent stac
k
or to a waste pipe.
Alternatively, the condensate may be discharged into the
rainwater system, or a purpose-built soa
k
away.
All connecting drainage pipewor
k
must have a fall of at
least
5
0 mm per metre run. It is recommended that the
pipe is insulated if run externally to minimise the effects
of freezing.
NOTE:
C
onnection of a condensate pipe to a drain may
be subject to local building regulations.
M
anual Air Vent
Using the manual air vent,
thoroughly vent air from
top of the heat exchanger
when filling the system to
save time during the boiler commissioning.
Note:
1
/4”
dia. manometer tube fits the manual vent.
Central Heating Pump & System By-pass
The central heating pump is factory fitted and an
automatic system by-pass is provided. The boiler can
be used in systems controlled by thermostatic radiator
valves (TRVs) but it is essential that the by-pass
isolating valve is fully open.
The circulating pressure and flowrate available for the
central heating system is shown opposite with the by-
pass in circuit.
MAX0022C
Promax
S
tore
RWC
Fill
up
the
Condensate
Trap
with
water
,
then
fit
to
the
boiler
Condensate
Drain
Pipe
500mm
supplied
(
suitable
for
21
.
5mm
overflow
pipe
)
Washer
S
eal
Boiler
Condensate
Connection
Optional
Route
-
DHW
Optional
Route
-
Condensate
L
ower
N
ut
Fig.
1
0a
© Baxi Heating UK Ltd 2015