26
9.0 Installation
© Baxi Heating UK Ltd 2016
9.7
Fitting The Flue
HORIZONTAL TELESCOPIC FLUE
1. There are two telescopic sections, the Terminal
Assembly and the Connection Assembly, a roll of sealing
tape and two self tapping screws. A 93° elbow is also
supplied.
2. The two sections can be adjusted to provide a length
between 315mm and 500mm (Fig. 24) when measured
from the flue elbow (there is 40mm engagement into the
elbow).
3. Locate the flue elbow on the adaptor at the top of the
boiler. Set the elbow to the required orientation (Fig. 25).
NOTE:
The flue elbow is angled at 93 degrees to
ensure a fall back to the boiler.
4. Measure the distance from the outside wall face to the
elbow. This dimension will be known as ‘X’ (Fig. 25).
5. If the distance from the flue elbow to the outside face of
the wall (‘X’ in Fig. 25) is less than 250mm the Connection
Assembly can be discarded and the Terminal Assembly
fitted directly into the elbow.
6. In instances where the dimension ‘X’ (Fig. 25) is between
250mm and 315mm it will be necessary to shorten the
Terminal Assembly by careful cutting to accommodate
walls of these thicknesses.
7. To dimension ‘X’ add 40mm. This dimension to be
known as ‘Y’.
8. Adjust the two telescopic sections to dimension ‘Y’ and
seal the joint with the tape provided (Fig. 27). Ensure that
the labels marked ‘TOP’ on the Terminal and Connection
Assemblies are uppermost.
9. Using the clearance holes in the Connection Assembly
secure it to the Terminal Assembly using the screws
supplied (Fig. 28).
Wall
Thickness
(X)
Wall Thickness
(X)
Fig. 24
Fig. 26
315mm
500mm
Terminal Assembly
Connection Assembly
Fig. 25
Fig. 27
‘Peak’ to be uppermost
Dimension ‘Y’
Securing Screw
Fig. 28
Sealing Tape
‘TOP’ Label
‘TOP’ Label
Содержание Promax 24 Combi ErP
Страница 56: ...56 Baxi Heating UK Ltd 2016 19 0 Notes ...
Страница 57: ...57 Baxi Heating UK Ltd 2016 19 0 Notes ...