Servicing
120
-393 632
.4 04.08 F
h
PARAMOUNT two 30 - 115 kW
65
Dismantling of the gas burner (PARAMOUNT two 80 D)
• Disconnect the connecting lines to the fan.
• Disconnect ionisation line.
• Disconnect ignition cable.
• Disconnect fastening screws of the bracket on the housing lid.
• Disconnect the screw connections of the gas connection pipe at
the mixing chamber and the gas valve.
• Remove the gas connection pipe and the gas injector.
• Disconnect the gas connection pipe at the gas valve and remove
gas valve.
• Undo the 5 fastening screws at the mixing chamber/heat ex-
changer.
• Remove bracket.
• Disconnect flue silencer from the bracket.
• Pull out the burner together with mixing chamber, fan and ea-
haust gas muffler to the front (see figure 19)siehe Abb. 21
• Clean burner pipe with soft brush.
Use new seals when installing.
Fig. 21: Dismantle of the gas burner (PARAMOUNT two 80 D)
Pull out burner with mixing cham-
ber and flue silencer.
Remove bracket.
Disconnect gas con-
nection pipe.
Remove gas injector.
Remove gas con-
nection pipe.
Remove gas valve.
Disconnect flue silencer from bracket (under
the housing lid).