Installation
120
-393 632
.4 04.08 F
h
PARAMOUNT two 30 - 115 kW
25
Attention! The boiler must not be operated at connecting pressu-
res outside the given areas!
The gas supplier has to be informed.
5.8
CO
2
-Content
The CO2-content in the flue must be checked during commissio-
ning and during regular maintenance of the boiler, as well as, after
reconstruction work on the boiler or on the flue system.
CO
2
-content during operation see section 3.2 „Technical Data
PARAMOUNT two” on page 13.
Too high CO
2
-values can lead to unhygienic combustion (high CO-
values) and damage to the burner.
Too low CO
2
-values can lead to ignition problems.
The CO
2
-value has to be set by modifying the gas pressure at the
gas valve.
5.9
Changing over from LPG to natural gas and vice versa
The gas type of the boiler must only be modified by an approved
gas installer.
• De-energise gas boiler.
• Close gas shut-off facility.
• Replace injector. Use enclosed new seals!
The CO
2
-content has to be set by setting the injector pressure at
the gas valve (section 5.11 „Guide Values for Injector Pressu-
re”).
The CO
2
-content at full load, as well as, low load must be between
the values according to section 3.2 „Technical Data PARAMOUNT
two” (page 13).