background image

5401587 - REV B   •   6/21

 PAGE 8 OF 10

Potter Electric Signal Company, LLC   •   St. Louis, MO   •   Phone: 800-325-3936   •   www.pottersignal.com

SignaLink

 Bridge

Wireless Supervisory System

WR - Wireless Repeater & WRX-R - Wireless Receiver

 

3.54 in

90 mm

 

 

4.72 in

120 mm

 

LIQUID TIGHT BREAK-THRU PLUG,REMOVE IF NEEDED TO INSTALL 

1/2” CONDUIT. .130-.450" [3.3-11.4mm] CABLE DIAMETER

 

2.38 in

60.50 mm

 

UV AND IMPACT RESISTANT POLYCARBONATE  UL94-5VA, NEMA 4, (IP 66) RATED ENCLOSURE

 

4.00 in

101.60 mm

 

 

1.65 in

41.91 mm

 

 

1.80 in

45.72 mm

 

O-RING

1/2" NPT CONDUIT CONNECTION

UV RESISTANT POLYCARBONATE  

UL94-5VA, NEMA 4, (IP 66) RATED ENCLOSURE

NUT

 

1.67 in

42.29 mm

 

Dimensions

Fig 5

WTX-M  - Transmitter

Fig 4

Содержание 0090221

Страница 1: ...ower of the fire panel or UL 864 or UL 1481 listed 24 VDC supply with battery backup See ordering information on page 10 for optional power supply Per UL 864 if the repeater is powered by batteries it...

Страница 2: ...on of metal file cabinets or shelving or changes to the interior of the building that could affect the signal path Document and keep as much information about the site survey as possible This will com...

Страница 3: ...mode Do not leave batteries in a device that is not installed as part of an active system with an operating receiver If a battery powered device does not receive confirmation from the receiver the dev...

Страница 4: ...output Remove the locknut from the threaded nipple of the Transmitter make sure the O ring is properly installed on the nipple and insert the nipple through the conduit opening of the device Install t...

Страница 5: ...to activate the pry off tamper on the back of the unit When mounting to a post follow the instructions that come with the post mounting kit to ensure that the pry off tamper on the back of the Repeate...

Страница 6: ...TE KEEP BATTERY OUT OF REACH OF CHILDREN AND IN ORIGINAL PACKAGE UNTIL READYTOUSE DISPOSEOFUSEDBATTERIESPROPERLY REPLACE BATTERY WITH BATTERIES DESCRIBED ABOVE USE OF ANOTHER BATTERY MAY PRESENT A RIS...

Страница 7: ...ternally connects the NO terminal and the EOLR resistor symbol terminal A loss of power or any trouble condition causes the relay to drop out and open the EOLR circuit this creates a trouble on the fi...

Страница 8: ...4 72 in 120 mm LIQUID TIGHT BREAK THRU PLUG REMOVE IF NEEDED TO INSTALL 1 2 CONDUIT 130 450 3 3 11 4mm CABLE DIAMETER 2 38 in 60 50 mm UV AND IMPACT RESISTANT POLYCARBONATE UL94 5VA NEMA 4 IP 66 RATED...

Страница 9: ...ndicate which WR the issue initiated from One 1 flash means repeater 1 TAMPER Amber Indicates the cover is removed from WTX M or WR or the WR has been removed from its mounting location COM ERROR Ambe...

Страница 10: ...ions Le present appareil numerique n emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioe...

Отзывы: