22
8-card Shelf CCC model 751109/15
3.1
Installing the 8-card Shelf on a Wall
Installations should conform to local practices and IEEE Std 487-2007 - IEEE
Recommended Practice for the Protection of Wire-Line Communication Facilities
Serving Electric Supply Locations.
3.2
Shelf Mounting
The 8-card Shelf CCC model 751109/15 should be installed as closely as possible
to the point of entry of the CO cable. Power will need to be routed to the shelf (-48
Vdc, 130 Vdc or 120 Vac).
A solid Station ground must be available, connected to the Station ground grid.
C
AUTION
Q
The equipment must be installed in a restricted area.
ATTENTION
ELECTROSTATIC
SENSITIVE
DEVICES
HANDLE ONLY AT STATIC
SAFE WORKSTATION
INCORRECT HANDLING MAY VOID WARRANTY
These procedures must be followed when handling an electrostatic sensitive
device.
•
A grounded wrist strap must be worn at all times during installation.
•
When unpacking, place the antistatic bag containing the device on an
electrostatic discharge (ESD) safe surface. An ESD safe surface is a
conductive surface connected directly to an earth ground.
•
When moving, carry the device in an ESD safe container or the antistatic
bag, provided with the device.
ESD Precaution
Содержание Teleline 751109/15
Страница 1: ...Teleline 8 card Shelf CCC model 751109 15 Description and Installation 925W751019 03E...
Страница 2: ......
Страница 5: ...Chapter 1 General Information...
Страница 12: ......
Страница 13: ...Chapter 2 Overview...
Страница 16: ...16 8 card Shelf CCC model 751109 15 Figure 1 8 card Shelf CCC model 751109 15...
Страница 20: ......
Страница 21: ...Chapter 3 Installation...
Страница 30: ...30 8 card Shelf CCC model 751109 15 Figure 3 Ground Strap Settings...
Страница 33: ...33 Cable Connections Figure 5 Station Side Terminal Blocks...
Страница 34: ...34 8 card Shelf CCC model 751109 15 Figure 6 Station Side Motherboard Interconnection Diagram...
Страница 55: ...Appendix A Acronyms...