ENGLISH
78
Copy factory parameters from device memory to Hot Key
programming stick
•
The device must be switched on.
•
Remove the four plastic plugs from the cover, unscrew the screws, and remove the cover.
Note!
Beware of live connectors.
•
Install the programming stick (A) in the Hot Key connector on the controller. The programming
stick cannot be inserted the wrong way round.
•
Press the
key for three seconds to display “HA”.
•
Use the arrow keys
and
to find the parameter “UPL”.
•
Press
the button until the UPL starts to flash. The parameters are copied from the device
memory to the programming stick. Finally, the text “End” appears on the display. Allow the text
to turn off before removing the programming stick.
•
When “End” appears on the display, you can remove the Hot Key stick.
•
Replace the cover.
Note!
If the controller and programming stick are not compatible, the text “Err” will be
displayed.
A
A
MED SAVE XW757K