The following manual digital output parameters are available:
•
Sply Fan Outp - Supply Fan Contactor
•
Rtn Fan Output - Return Fan Contactor Aux Air 1
•
Output - Auxiliary Air Heating Stage 1 Relay
•
Aux Air 2 Output - Auxiliary Air Heating Stage 2 Relay
•
Aux Air 3 Output - Auxiliary Air Heating Stage 3 Relay
•
Aux Wtr 1 Output - Auxiliary Water Heating 1 Relay
•
Aux Wtr 2 Output - Auxiliary Water Heating 2 Relay
•
Alarm Output - Alarm Output Relay
•
S1 Cmpr 1 Output - Compressor 1A Contactor (Scrolls); Sys 1 Compressor Contactor (Recip)
•
S1 Cmpr 2 Output - Compressor 1B Contactor (Scrolls); Sys 1 Stage 2 Unloader (Recip)
•
S1 Cmpr 3 Output - Compressor 1C Contactor (Scrolls); Sys 1 Stage 3 Unloader (Recip)
•
S1 AC Sol Output - System 1 AC Solenoid Valve
•
S1 Liq #1 Output - System 1 Liquid Solenoid Valve 1
•
S1 Liq #2 Output - System 1 Liquid Solenoid Valve 2
•
S1 Wtr Sl Output - System 1 Water Heating Solenoid Valve
•
S1 Reh 1 Output - System 1 Air Reheat Solenoid Valve 1
•
S1 Reh 2 Output - System 1 Air Reheat Solenoid Valve 2
•
S1 RH Sft Strt - System 1 Air Reheat Solenoid Valve 4
•
S2 Cmpr 1 Output - Compressor 2A Contactor (Scrolls); Sys 2 Compressor Contactor (Recip)
•
S2 Cmpr 2 Output - Compressor 2B Contactor (Scrolls); Sys 2 Stage 2 Unloader (Recip)
•
S2 AC Sol Output - System 2 AC Solenoid Valve
•
S2 Liq #1 Output - System 2 Liquid #1 Solenoid Valve
•
S2 Liq #2 Output - System 2 Liquid #2 Solenoid Valve
•
S2 Wtr Sl Output - System 2 Water Heating Solenoid Valve
•
S2 Reh 1 Output - System 2 Air Reheat Solenoid Valve 1
•
S2 Reh 2 Output - System 2 Air Reheat Solenoid Valve 2
•
Exh Fan Output - Exhaust Fan Contactor
•
Spl 1 Dig Output - Special Option Digital Output Relay 1
•
Spl 2 Dig Output - Special Option Digital Output Relay 2
•
S2 RH Sft Strt - System 2 Air Reheat Solenoid Valve 4
•
S2 Cmpr 3 Output - Compressor 2C Contactor (Scrolls); Sys 2 Stage 3 Unloader (Recip)
Analog Output
Each analog output of the ECC III may be controlled individually by setting the corresponding parameter.
The following analog output parameters are available:
• Exh Dpr Pos - Exhaust Air Damper Actuator Position
•
Rcrc Dpr Pos - Recirculation Air Damper Actuator Position
•
Outs Dpr Pos - Outside Air Damper Actuator Position
• AuxAirHtSig - Auxiliary Air Heating Control Valve Position
•
Spl1AlgOut - Special Option Analog Output 1
•
Spl2AlgOut - Special Option Analog Output 2
•
Spl3AlgOut - Special Option Analog Output 3
•
Spl4AlgOut - Special Option Analog Output 4