
28
EGW05-SWHPEG-20140724
TM
TM
Table 3-17. Water Cooled Condenser Performance
SWHP Model
Cooling Tower Water Condenser
1
Chilled Water Condenser
2
Heat Rejection
3
gpm
Water (Feet)
4
gpm
Water (Feet)
5
Mbtu/hr
060
25
28
25
24
230
080
35
32
25
31
310
100
40
29
35
23
350
120
50
30
40
18
450
140
60
33
50
27
520
190
70
32
60
27
600
220
80
31
70
24
350/350
6
260
100
32
80
20
450/450
6
300
120
35
100
28
520/520
6
340
140
34
120
28
600/600
6
1
Maximum 90
o
F EWT
2
Maximum 55 F EWT
3
Heat rejection at 120 F Condensing Temperature
4
Cleanable, vented condenser
5
Spiral, vented condenser
6
Two circuit water-cooled condenser, one for each compressor
NOTE
Contact factory if water-cooled condenser line length is more than 100 ft and/or the
water-cooled condenser is located more than 20 feet below the PoolPak.