23
EGW05-SWHPEG-20140724
TM
TM
Table 3-11. ACC - Model SWHP 0220
Model 0220**
Ambient
Air (ºF)
ACC Model
Number
Fans
Refrigerant
Circuits
Refrigerant Line Size
Weight
ACC Voltage
FLA
MCA
MOP
wide
long
Hot Gas
Liquid
Lbs
95/100º
ACC0734
2
2
Two
2@
1-5/8
2@
1-1/8
1340
208/230-3-60
28.0
29.8
45.0
460-3-60
14.0
15.0
20.0
575-3-60
11.2
15.0
15.0
ACC0864
2
2
Two
2@2-1/8
2@1-3/8
1440
380-3-50
11.7
15.0
20.0
105º
ACC0994
2
3
Two
2@
2-1/8
2@
1-3/8
1990
208/230-3-60
42.0
43.8
60.0
460-3-60
21.0
21.9
30.0
575-3-60
16.8
20.0
25.0
ACC1094
2
3
Two
2@2-1/8
2@1-3/8
1990
380-3-50
17.5
21.9
30.0
110º
ACC1374
2
3
Two
2@
2-1/8
2@
1-3/8
2210
208/230-3-60
42.0
43.8
60.0
460-3-60
21.0
21.9
30.0
575-3-60
16.8
20.0
25.0
380-3-50
17.5
21.9
30.0
115º
ACC1974
2
5
Two
2@
2-1/8
2@
1-3/8
3410
208/230-3-60
70.0
71.8
90.0
460-3-60
35.0
35.9
45.0
575-3-60
28.0
28.7
35.0
380-3-50
29.2
35.9
45.0
** Dimensions - see Air Cooled Condenser dimension views with number of fans wide (end) and number long (side)
PPK_R410A_ACC_Summary_20110104.xls
Table 3-12. ACC - Model SWHP 0260
Model 0260**
Ambient
Air (ºF)
ACC Model
Number
Fans
Refrigerant
Circuits
Refrigerant Line Size
Weight
ACC Voltage
FLA
MCA
MOP
wide
long
Hot Gas
Liquid
Lbs
95/100º
ACC0864
2
2
Two
2@2-1/8
2@1-3/8
1440
208/230-3-60
28.0
29.8
45.0
460-3-60
14.0
15.0
20.0
575-3-60
11.2
15.0
15.0
ACC0994
2
3
Two
2@2-1/8
2@1-3/8
1990
380-3-50
17.5
21.9
30.0
105º
ACC1094
2
3
Two
2@2-1/8
2@1-3/8
1990
208/230-3-60
42.0
43.8
60.0
460-3-60
21.0
21.9
30.0
575-3-60
16.8
20.0
25.0
ACC1294
2
3
Two
2@2-1/8
2@1-3/8
2140
380-3-50
17.5
21.9
30.0
110º
ACC1654
2
4
Two
2@
2-1/8
2@
1-3/8
2730
208/230-3-60
56.0
57.8
70.0
460-3-60
28.0
28.9
35.0
575-3-60
22.4
23.1
30.0
380-3-50
23.3
28.9
35.0
115º
ACC2444
2
5
Two
2@
2-1/8
2@
1-3/8
3660
208/230-3-60
70.0
71.8
90.0
460-3-60
35.0
35.9
45.0
575-3-60
28.0
28.7
35.0
380-3-50
29.2
35.9
45.0
** Dimensions - see Air Cooled Condenser dimension views with number of fans wide (end) and number long (side)
PPK_R410A_ACC_Summary_20110104.xls